ADTRAN HDSL2 Battery Charger User Manual


 
TOTAL ACCESS BATTERY BACKUP UNIT (BBU) P/N 1175044L4
WITH OPTIONAL HDSL2 SUPPORT
For more detailed documentation, visit us online at www.adtran.com
Quick Start Guide, 61175044L4-13B, February 2002 Technical Support 1-888-4ADTRAN (1-888-423-8726) Copyright 2002 ADTRAN, All Rights Reserved
I
NSTALLATION
I
NSTRUCTIONS
1. Unpack the Total Access BBU and inspect for damage. If damage is
apparent, refer to your carrier or supplier for remedy.
2. The BBU must be mounted with the following minimum clearance:
Top — 1”
Bottom — 3”
Left Side — 1”
Right Side — 10”
3. Using the template provided, mark and drill three pilot holes using a
size I (0.228" Dia.) drill bit.
4. Insert 1/4” x 3/4” pan-head wood screws (supplied) into the three pilot
holes, leaving 1/8” space between the screw-head and the plywood.
5. With an assistant, mount the battery box on the three support screws on
the plywood.
6. Connect the Battery Backup Unit to the Total Access 750 or 850 as shown in
the connection illustration above. Use cable tie-downs as appropriate.
A
CCESSORY
L
IST
(I
TEMS
SHIPPED
WITH
UNIT
)
1. Three 1/4” x 3/4” pan-head wood mounting screws
2. One mounting template
3. One 24” straight-through cable for T1 connection to the Total Access 750
4. One 6” tie wrap
5. One tie wrap/cable holder
B
attery B
acku
p
1175044L4
R1-I
T1-I
R-O
T-
O
LX IN
LY IN
EU2
LX OUT
LY OUT
EU1
MLT-A
MLT-B
-48ALM
MJ
MJR
MJV
MJVR
-48 R
P2
-48 V
V.35
T1
FT1
MANAGEMENT
DC
POWER
WARNING:
20 Hz FUSE
MUST BE REMOVED
BEFORE REMOVING COVER.
Terminal
access
cover
-54 VDC Output to TA 750
WARNING:
SCREW LENGTHS EXCEEDING 3/8"
MAY PUNCTURE BATTERIES
1175044L4
BATTERY BA
CKUP
Total Access 750
-48 VDC Backup Battery Unit
During TA 750 wall installation,
position the chassis so front panels
face up.
CAUTION
* Note: Connection above will be different for TA 850 Units
G
ROUNDING
I
NSTRUCTIONS
The equipment grounding conductor is to be connected to ground at the service
equipment at all times. Bare, covered, or insulated grounding conductors are
acceptable.
R
EMOTE
HDSL2 C
ARDS
Part Number Description
1222024L6 T200 H2TU-R 24-48 VLT LCL PWR
1222024L7 T200 H2TU-R 24-48 VLT LCL PWR