ADTRAN 750 Battery Charger User Manual


 
1Section 61175043L2-5, Issue 161175043L2-5A
Section 61175043L2-5A
Issue 1, June 2000
CLEI Code # SIMPAADA _ _
Total Access
750/850
AC/DC Power Supply and Battery Charger
Installation and Maintenance
1. GENERAL
This practice provides installation and maintenance
procedures for the ADTRAN
Total Access 750/850
Power Supply/Battery Charger. Figure 1 is a front
and back illustration of the PS/BC.
Revision History
This is the initial release of this document. Future
revisions will be made in this subsection.
Features
The Total Access 750/850 PS/BC, P/N 1175043L2,
features include the following:
Compact design.
Versatile mounting arrangements.
All mounting hardware included.
Built-in Fuse.
Multi-feature status LED.
Modular connections.
Positive ground.
Uninterrupted power output if battery backup
connected.
FCC and UL 1950 compliant.
Figure 1. TA 750/850 PS/BC, Front and Back
Trademarks: Any brand names and product names included in this document are
trademarks, registered trademarks, or trade names of their respective holders.
2. DESCRIPTION
The AC/DC Power Supply/Battery Charger provides
-54 VDC to the Power Supply Unit in the TA 750/850
Chassis. The PS/BC receives 115 VAC through a
standard plug and wall socket. The unit works in
conjunction with an optional ADTRAN backup
battery pack, P/N 1175044L1, L2, L3. In this
arrangement, the PS/BC maintains the battery at peak
charge of -54V. If AC power is lost, the unit
automatically transfers power from the battery pack
without interrupting service. When AC power returns,
the unit switches back to AC power and recharges the
battery to peak charge.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2), this device must accept any interference that
may cause undesired operation.
Changes or modifications not expressly approved by
ADTRAN could void the user’s authority to operate
this equipment.
GRN - OK
YEL - DISCHARGING
RED - LOW
OFF - NOT CONNECTED
GRN - OK
YEL - FAIL
RED - FAIL
OFF - FAIL
1175043L2
AC BAT
1175043L2
3 AMP
-54V ,
2A OUTPUT
120 VAC/
2A 60HZ INPUT
THIS UNIT MAY BE
POWERED BY 2
SOURCES. DISCONNECT
BOTH SOURCES BEFORE
SERVICING.
-48V ,
2A INPUT
AC ALARM
OUTPUT
9902271
F
U
S
E
F
U
S
E
Contents
1. GENERAL ................................................................... 1
2. DESCRIPTION ............................................................ 1
3. INSTALLATION.......................................................... 2
4. SPECIFICATIONS....................................................... 4
5. MAINTENANCE......................................................... 4
6. WARRANTY AND CUSTOMER SERVICE .............. 4
Figures
Figure 1. TA 750/850 PS/BC, Front and Back ................... 1
Figure 2. AC/DC Power Supply Battery Charger Layout .. 3
Figure 3. Alternate Mounting Arrangements ...................... 3
Tables
Table 1. Alarm Relay Operation........................................ 2
Table 2. LED Indication .................................................... 2
Table 3. Specifications....................................................... 4