Cooper Lighting 232 Work Light User Manual


 
Metalux • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
12/11/2007 7:51:43 AM
Specifications and Dimensions subject to change without notice.
ADF020715
ORDERING INFORMATION
PHOTOMETRICS
ACCESSORIES
SHIPPING INFORMATION
STN
SAMPLE NUMBER: STN-232-120V-EB81-U
Number of Lamps
1 or 2 lamps
(Not Included)
Wattage (Length)
40=34/40W T12 (48")
32=32W T8 (48")
Voltage
(1)
120V=120 Volt
277V=277 Volt
347V=347 Volt
UNV=Universal
Voltage 120-277
(2)
Blank=4' Length
8T=8' Length
STN=Series
Options
GL=Single Element Fuse
GM=Double Element Fuse
Emergency=EM Installed
Options
RIF1=Radio Interference
Suppressor
6-3/18 SJT-C&P-515P=Cord
& Plug (120V)
6-3/18 SJT-C&P-L715P=
Cord & Plug (277V)
PI/CPI=Plug-In Option
L715P=Cord & Plug (277V)
TILW=Tandem In-Line
Wiring Option (Consult
TILW Option Catalog Page)
(See options & accessories)
Packaging
U=Unit Pack
4B=4 Bulk
Ballast Type
(1)
EB8 =T8 Electronic Instant Start.
Total Harmonic Distortion < 10%
EB8 /PLUS=T8 Electronic Instant Start.
High Ballast Factor >1.13. Total
Harmonic Distortion < 20%
ER8
=T8 Electronic Program Rapid Start.
Total Harmonic Distortion < 10%
EB2
=T12 Electronic Rapid Start.
DLS=Digital Lighting System Dimming
No. of Ballast
1, 2 or 3
No. of
Ballast
1, 2 or 3
No. of Ballast
1 or 2
No. of Ballast
1 or 2
Candela
Angle Along II 45
o
Across
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
1009 1009 1009
996 1001 1009
942 979 1014
853 945 1026
735 898 1008
593 823 959
432 721 906
260 633 824
100 460 600
9 248 381
7 336 527
7 255 448
7 211 364
7 142 276
7 76 175
7 18 79
7 5 5
0 0 0
0 0 0
Coef
ficients of Utilization
Effective floor cavity reflectance 20%
rc 80% 70% 50% 30% 10% 0%
rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
RCR
0
1
2
3
4
5
6
7
8
9
10
Zonal Lumen Summary
Zone Lumens %Lamp %Fixture
0-30
0-40
0-60
0-90
90-180
0-180
||
STN-232
Electronic Ballast
F32T8/35K Lamps
2850 Lumens
Spacing criterion:
(II) 1.3 x mounting
height, () 1.5 x
mounting height
Efficiency 93.5%
Test Report:
STN232.IES
LER = FS-80
Yearly Cost of 1000
lumens, 3000 hrs at
.08 KWH = $3.00
822 14.4 15.4
1397 24.5 26.2
2724 47.8 51.1
4250 74.6 79.8
1078 18.9 20.2
5328 93.5 100.0
107 107 107 107 102102 102 102 93 93 93 85 85 85 78 78 78 75
95 90 86 81 91 86 82 78 79 75 72 72 69 67 65 63 61 58
86 77 70 64 81 74 67 62 67 62 58 61 57 53 56 53 50 46
78 67 59 52 74 64 57 51 59 53 47 54 49 44 49 45 41 38
71 59 50 44 67 56 48 42 52 45 40 47 42 37 43 38 35 32
64 52 43 36 61 49 41 35 45 38 33 41 35 31 38 33 29 26
59 46 37 31 56 44 36 30 40 33 28 37 31 26 34 29 25 22
54 41 32 26 51 39 31 26 36 29 24 33 27 23 30 25 21 19
50 37 28 23 47 35 27 22 32 26 21 30 24 19 27 22 18 16
46 33 25 19 43 31 24 19 29 22 18 27 21 17 24 19 16 14
43 30 22 17 40 29 21 17 26 20 16 24 19 15 22 17 14 12
(Order Separately)
A1B=Spacer
GRP-STN=Gripper Hanger (Use 2 Per Fixture)
AYC-Chain/Set=36" Chain Hanger (Use 1 Set Per Fixture)
SCF=Fixed Stem Set (Specify Length)
SCS=Swivel Stem Set (Specify Length)
ATG-4=Tong Hanger (Use 2 Per Fixture)
DI2=Long Connector
STN/SS-ASY-3
(3)
=3" Asymmetric Reflector (Specify 2', 3', or 4')
STN/SS-ASY/REV-3
(3)
=3" Asymmetric Reverse Reflector
(Specify 2', 3', or 4')
STN/SS-SYM-6
(3)
=6" Symmetric Reflector (Specify 2', 3', or 4')
STN/SS-ASY-6
(3)
=6" Asymmetric Reflector (Specify 2', 3', or 4')
IC-4FT-REFL
(3)
=12" Symmetric Reflector
WG/SS-4FT=Wire Guard
(Additional Accessories Available. See Options and Accessories Section.)
STN-132
12 lbs.
8TSTN-132 20 lbs.
STN-232 12 lbs.
8TSTN-232 24 lbs.
Catalog No. Wt.