Cooper Lighting AEL1SD Work Light User Manual


 
602
EMERGENCY LIGHTS Architectural
COOPER LIGHTING
COOPER LIGHTING - SURE-LITES
®
Dual-voltage input
120/277VAC, 60Hz
Die cast aluminum housing
with powder coat finish
Three 6V 6W High output
Xenon lamps
Sealed Nickel Cadmium
Battery Maintenance Free,
Long Life, Full Recharge
time, 24 Hours
Watchguard EMS Self-
Diagnostic System
Photocell Test Switch
(requires accessory LASER
for activation)
Universal Pattern
Knockouts on rear of
housing for direct
mounting to junction box
UV Stable Polycarbonate
Lens
Line-Latching, Solid-state
Voltage Limited Charger,
Low-Voltage Disconnect,
Brownout Circuit,
Overload/Short Circuit
Protection, Test
Switch/Power Indicator
Light
UL 924 Listed Self-
Diagnostics, UL Outdoor
Wet Location Listed
(suitable for wet and damp
locations), Life Safety NFPA
101, NEC/OSHA, Most
State and Local Codes
ENERGY DATA
AEL1SD
Input Current (Max.)
120V = .10A
277V = .07A
ARCHITECTURAL
EMERGENCY
LIGHT SERIES
DIE CAST ALUMINUM
Emergency Light
DIMENSIONS
DESCRIPTION
The Sure-Lites Architectural
Emergency Light is designed to
provide superior illumination
while blending into the
surrounding space. The housing
is constructed of die cast
aluminum with an integral
refractive polycarbonate lens. The
emergency light’s advanced
optical design in conjunction with
high output Xenon lamps provide
maximum path of egress lighting
performance. The Sure-Lites
Architectural Emergency Light is
listed for temperatures between -
20°C and 40°C (-4°F and 104°F)
and has silicone gaskets that
provide protection from moisture
and rain. [Remote unit
temperature range: -40°C and
65°C (-40°F and 149°F)] Standard
features include Watchguard EMS
self-diagnostic system which
meets NFPA 101 testing
requirements and a FasTest
photocell which enables remote
testing of the emergency light.
Family
AEL1=Architectural
Emergency
Light
ORDERING INFORMATION
SAMPLE NUMBER: AEL1SD
Housing
Finishes
Blank=Silver
BK=Black
BZ=Bronze
WH=White
SD=Self Diagnostics
(Standard)
Options
TDM=Time Delay
Monitor
Remote=Remote
Unit
Accessories (order separately)
LASER=Key Chain, Red Laser
Pointer (activation
tested at 15 feet)
10 7/8”
[276.23mm]
3 7/8”
[98.43mm]
7”
[177.8mm]
Self-Diagnostics
The self-diagnostic unit will
automatically perform all tests
required by UL924, and NFPA
101. The system indicates the
status of the exit at all times
using the LED indicator near the
test switch on the side of the
unit. A 90 minute battery power
(emergency mode) simulation
test will occur randomly once
every six months.
ELECTRICAL RATINGS
Model DC Voltage 1 1/2 Hours
AEL1SD 6 18
Rated Wattageto 87 1/2% of Rated D.C. Voltage Lamp Information
Type Wattage Number Spacing
1
Xenon 6 each 11549423 30.0'
(1)
The "Rule of Thumb" spacing guidelines are designed to achieve 1 foot-candle average and 0.1 foot-candle minimum with a 40:1
maximum/minimum ratio. The corridor used is 100 feet long, 9 foot ceiling with a 6 foot wide walkway and 3 foot path of egress.
The reflectances are 80% ceiling, 50% walls and 20% floors. The fixture mounting height is 8.5 feet. Cooper Lighting assumes no
responsibility for local requirements or specific project variables. This is a guideline to be used as a design aid, not as guarantee of any code
compliance.
AEL1WHSD
AEL1BKSD
AEL1BZSD
AEL1