7-114
CALL(P)
Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
an error code is stored into SD0.
• The device specified for the argument cannot be secured for the data size.
(Error code: 4101)
• Following the execution of the CALL (P) instruction, an END, FEND, GOEND, or STOP
instruction is executed before the execution of the RET instruction.
(Error code: 4211)
• An RET instruction is executed prior to the execution of the CALL (P) instruction.
(Error code: 4212)
• A 17th nesting level is executed. (Error code: 4213)
• There is no subroutine program for the pointer specified in the CALL (P) instruction.
(Error code: 4210)
Program Example
(1) The following program executes a subroutine program with argument when X20 is turned
ON.
[Ladder Mode] [List Mode]
Step
Instruction
Device