Philips MJ5 Work Light User Manual


 
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • A0508
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
MJ5 Exit Signs MJ5
Page 1 of 1 Chicago Exit Signs
Lightolier is a Philips group brand
Features
1. Illumination: AC Light Source: Standard exit face illumination is provided
by two 7 watt PL type fluorescent lamps. Letter brightness and illumination
uniformity exceed UL requirements with both incandescent and fluorescent
models. Emergency Light Source: Exit illumination in all models is provided by two
6 volt, 5.4 watt wedge base incandescent DC lamps. MJ5E-DEH combination
models with side mounted lighting heads are provided with 6 volt, 12 watt
halogen bi-pin lamps.
2. Housing: MJ5 Series exits are constructed of heavy duty steel finished
in white baked-on powder paint providing scratch and corrosion resistance.
Exit face features 6” letters with 3/4” stroke on translucent glass panels and
Full length directional arrows to meet City of Chicago visibility requirements.
Mounting canopy is standard.
3. Electronics: 120/277 VAC dual voltage input with surge-protected,
solid-state circuitry. Fully automatic, temperature compensating, variable rate
float charging system is complete with low voltage disconnect, AC lockout,
brownout protection, AC indicator lamp and test switch.
4. Battery: Maintenance-free, sealed, lead calcium battery has an
estimated service life of 5 years, and an operating temperature range of 65°F
(19°C) to 85°F (30°C).
5. Input Power Requirements: AC Only: 19W; Emergency Operation: 29W
6. Warranty: Unit: (excluding lamps) 3-years full coverage against defects
in materials and workmanship from date of shipment. Battery: 3 years full
warranty plus an additional 7 years of pro-rata coverage
Code Compliance
All models are UL Listed and meet NFPA 101 Life Safety Code, NEC, OSHA and City
of Chicago codes. Emergency models are UL924 Listed.
Options
DEH = Combination Model w/ Side Mounted Par 36 12W Halogen Heads
277 = 277VAC, 60Hz. Input (AC models only)
SW = Special Wording (consult factory)
SX = Self-Diagnostic Circuit (emergency models only)
IA = Audible Intermittent Alarm (emergency models only)
IV = Visual Intermittent Alarm (emergency models only)
FA = Fire Alarm Panel Interface
INC = Two candelabra base 15T6 120 volt, 15 watt incandescent AC lamps.
Accessories
MJSKW = 18” Stem Mounting Kit (white)
MJSKB = 18” Stem Mounting Kit (black)
MJPG9 = Wire Guard - Wall Mount (AC and emergency models)
MJPG10 = Wire Guard - Wall Mount (combination models)
Fluorescent or optional incandescent lamp AC-only and emergency exit models meet Chicago requirements. Rugged steel signs for wall, ceiling or end mount applications.
How to Specify:
MJ5
MJ5 =Chicago Exit
A B C D E
12.75” 9.5” 14.5” 2.5” 26.25”
32.4cm 24.1cm 36.8cm 6.4cm 66.7cm
SERIES MODE OF # OF LETTER EXIT FACE
OPERATION FACES COLOR DESIGNATOR
Single Face Models
3 = EXIT (No Arrow)
6 = EXIT (Right Arrow)
9 = EXIT (Left Arrow)
12 = EXIT (Double Arrow)
2 = STAIRS (No Arrow)
5 = STAIRS (Right Arrow)
8 = STAIRS (Left Arrow)
11 = STAIRS (Double Arrow)
1 = Single face
2 = Double face
RW = Red on
White
Double Face Models
18 = EXIT (No Arrow)
21 = EXIT (Right or
24 = EXIT (Double Arrow)
17 = STAIRS (No Arrow)
20 = STAIRS (Right or
Left Arrow)
23 = STAIRS (Double
Arrow)
RW
A = AC Only Exit
E = Emergency
Operation Exit
Standard Exit Combination Model (DEH option)