2
Vert-I-Pak
®
Chassis Specifications
MODEL:
-410AR-410AR-410AR
25 = 2.5 KW
34 = 3.4 KW
ENGINEERING CODE
OPTIONS
DESIGN SERIES
SERIES
See Charts A & B (page 11)
.3” water .3” water .3” water
Heater Watts 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090 2500/2050 3400/2780 5000/4090
Voltage
Heating BTU/h 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900 8500/7000 11600/9500 17000/13900
Heating Current (Amps) 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7 10.9/9.9 14.8/13.4 21.7/19.7
Minimum Circuit Ampacity
15 19.9 28.6 15 19.9 28.6 15 19.9 28.6
Branch Circuit Fuse (Amps) 15 20 30 15 20 30 15 20 30
LRA - Compressor (Amps) 22 22 22 30 30 30 42 42 42
Cooling Current (Amps) 4.2/4.4 4.2/4.4 4.2/4.4 5.2/5.4 5.2/5.4 5.2/5.4 8 1/8.. 6 8 1/8.. 6 8 1/8.. 6
Basic heater Size 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw 2.5 Kw 3.4 Kw 5.0 Kw
Power Connection
HARD WIRED HARD WIRED HARD WIRED
Electrical Data
NOTES:
Important: All 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electrica
requirements. See Figure 15, page 13 for unit wiring and wall thermostat wiring. See page 12 for wire size. Use
HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with NEC and local codes.
General Specifications
23 1/8”
23 1/8”
32 1/4”
26” x 28 1/2” x 35”
23 1/8”
23 1/8”
32 1/4”
26” x 28 1/2” x 35”
23 1/8”
23 1/8”
32 1/4”
26” x 28 1/2” x 35”
Recommended Branch
Circuit Wire Sizes
* AWG-American Wire Gauge
14 12 10 14 12 10 14 12 10