Charles Bentley & Son AA Series Battery Charger User Manual


 
Ordering Information
Optional Accessories
Remote summary relay
• Battery temperature
compensation
Low DC voltage alarm relay
High DC voltage alarm relay
Current failure relay
Combined Low/High voltage
alarm relays
AC power failure relay
Specifications
AC Input 108-132 volts/60 Hz (220 volts/50 Hz optional)
Operating Temperature 0º to 50º C (32º to 122º F)
Storage Temperature -20º to 60º C (-4º to 140º F)
Cooling Convection
DC Output
- Float 2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium
- Equalize 2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium
Current Limit Approximately 135%
Enclosure 304 stainless steel hinged cover to facilitate installation
12 Volt
Model
Number
Height
Inches
Width
Inches
Depth
Inches
Approx.
Weight
D.C. Output
Amps
System
Voltage
24 Volt
32 Volt
AA1206* 6 12 11 9 8.5 12
AA1210* 10 12 11 9 8.5 14
AA1220* 20 12 11 9 8.5 22
AA2406* 6 24 11 9 8.5 14
AA2410* 10 24 11 9 8.5 22
AA2420* 20 24 13 16.5 8.5 38
AA3206 6 32 11 9 8.5 22
AA3210 10 32 11 9 8.5 26
0 102030405060708090100
% OF RATED CHARGING CURRENT (AMPS)
VPC
2.5
2.4
2.3
2.2
2.1
2.0
1.9
1.8
Equalize
Float
Typical Output Curve
*UL Listed
Contact your Charles sales representative for specific
product information.
When ordering, please specify:
1. Model number
2. AC input: voltage & frequency
3. Battery type and number of cells
4. Ampere-hour capacity of battery
5. Recharge time desired
6. Description of load
7. Options
Charles Industries, Ltd.
Industrial Group
5600 Apollo Drive
Rolling Meadows, IL 60008 USA
Voice: (847) 806-6300
Fax: (847) 806-6352
E-mail: mktserv@charlesindustries.com
D-IND001-B01 Rev. 3
IS0 9000
REGISTERED
QUALITY SYSTEM