- 6 -
Fig.1.
Fig.2.
Fig.3.
(A)
(B)
(D)
(C)
(L)
(K)
Fig.4.
(G)
(F)
Connect the compressor to the power supply.
Always turn on and off by the appropriate switch.
TURNING ON AND OFF (DA6/200/DA6/201,
DA25/180, DA25/200 - NOT DA200): THE ON/
OFF SWITCH.
(A) Fig.1. is located on the top of the pressure
switch box.
These compressors are controlled by a pressure
switch assembly (B) Fig.2. which automatically
cuts off the power supply to the motor when
the upper limit is reached and restarts the
compressor automatically when the pressure
drops below the minimum.
TURNING ON AND OFF (DA200 ONLY):
This compressor is operated by a manual
on/off switch (F) Fig.4. and NOT by an
automatic pressure switch as fitted to the other
compressors shown in this booklet.
WARNING (DA6/200/DA6/201, DA25/180,
DA25/200):
The pressure switch is set at the factory and the
compressor is also fitted with a safety valve in
the event of the pressure switch not functioning
correctly.
SETTING THE REQUIRED AIR PRESSURE:
DA25/180, DA25/200
Close the air outlet valve (C) Fig.2. and adjust
pressure by turning the knob on the pressure
regulator valve (D) Fig.2. clockwise to increase
pressure. Should it be necessary to decrease
pressure open the the air outlet valve (C) Fig.2.
slightly and then turn the pressure regulator
valve knob (D) anticlockwise, re-close air outlet
valve (C).
DA200
This compressor is fitted with a pressure
regulator unit (G) Fig.4. so the pressure may be
regulated as necessary. To increase the pressure
turn the knob clockwise, to decrease the
pressure turn the knob anticlockwise.
DA6/200
Close the air outlet valve (K) Fig.3. and adjust
pressure by turning the knob on the pressure
regulator valve (L) Fig.3. clockwise to increase
pressure. Should it be necessary to decrease
pressure open the the air outlet valve (K) Fig.3.
slightly and then turn the pressure regulator
valve knob anticlockwise, re-close air outlet
valve.
COMPRESSOR OPERATION