Greenheck Fan QEI-L Nail Gun User Manual


 
10
Certifications & Listings
Seismic Certification
TheInternationalBuildingCode(IBC)hasbeenadoptedatthestateandlocal
levelthroughouttheUnitedStates.Withtheadoptionofthiscode,comesthe
introductionofstandardsintendedtoimprovetheperformanceanddesignof
non-structuralsystemssubjecttoseismicevents.
QEI-I/II and QEID
• Meetthe2006IBC,2009IBC
• CaliforniaOSHPDrequirements(horizontalmountonly)OSP0223-10
• Shaketabletestedatanindependenttestfacilityinaccordancewith
ICC-ESAC156
• Allequipmentcertifiedtoworstcasescenarioseismicconditions
- Importancefactorof1.5(IP=1.5) - OccupancyCategories(I-IV)
- SiteClasses(A-F) - SeismicDesignCategories(A-F)
ConsultyourGreenheckrepresentativeorvisitgreenheck.com/seismicformoredetails.
UL 762 Restaurant Exhaust
Inlinegreaseexhaustfansareanexcellentalternativefor
kitchenapplicationswhenrooforwallmountedventilators
arenotpractical.AQEI-I/IIwithUL762greaseoptionis
designedtowithstandthedemandsofhightemperature
kitchengreaseexhaustandhigh-pressureductwashers.
A Tough Package to Beat
TheQEI-I/IIinlinegreasefanistoughtobeatwhen
packagedwithourfulllineofkitchenhoodsandgrease
extractionoptions.TakeadvantageofGreenheck’s
expertiseinprovidingatotalsolutioninkitchenventilation
equipment.
UL762isconcernedwithfansdesigned
forremovalofsmokeandgreaseladen
vaporswithairstreamtemperaturesup
to400°F.
•MeetsallUL705requirements
•UL/cULFileMH11745
UL/cULPowerVentilatorsfor
RestaurantExhaustAppliances
•Boltedaccessdoor
•Drainconnection
•MeetsrequirementsofNFPA96
VentilationControlandFireProtection
ofCommercialCookingOperations
ListedPower
Ventilationfor
Restaurant
Exhaust
Appliances
13G3Maximum
Operating
Temperature
400°F.
UL 705 Power Ventilator
QEI-L,QEI-I/IIandQEIDmodelsareavailablewiththeUL/cUL705(UnderwritersLaboratory)listingonawide
varietyof50and60Hzmotors.ThislistingensurestheuseofULapprovedelectricalcomponents.
MotorsareavailableaseitherIEC(IP55)orNEMA(TEAOorODP)designs.IECdesign
motorsareadjustablespeeddrive(ASD)compatible,haveclassFinsulationandare
capableofwye-deltastartingwhenover5.5kW.NEMAmotorsuseacrosstheline
startingwithoptionsforASDcompatibility.Motor(IECorNEMA)using50Hzpowerhave
a1.0servicefactor,while60Hzpowerhave1.15
servicefactor.Designandconstructionoptions
formotorsincludeincreasedthermalinsulation,
overloadprotectionandextendedmotorleads.
UL/cULFileE40001
UL/cULListedPowerVentilator
UL Emergency Smoke Evacuation
QEI-I/IIandQEIDmodelsweretestedand
ratedfordesigntimeandtemperatureused
inemergencyheatandsmokeexhaust
applications.
UL/cULFileMH17511
UL/cULPowerVentilatorsforSmokeControlSystems
Rice Engineering Inc
Jeremy J. Klaas
08-08-05J
QEI-54 Class I
Mar 5, 2009 at 5:39 PM
090224 EQZ .r3d
Y
XZ
Tau Bot
psi
7880
7090
6300
5510
4720
3930
3140
2350
1560
770
-20
Results for LC 3, EQ neg Z di r (0.7*4.5)
Structural Finite Element Analysis
Seismic Design Category F
Model
Operating
Temperature
Time
Duration
ºC ºF Hours Comments
QEID 300 572 1
PerBritishSpec7346
QEI-I/II 300 572 2
QEI-I/II 260 500 4
PerIndustrialRisk
Insurers(NorthAmerica)
QEID 260 500 5
ConsultyourGreenheckrepresentativefortimeandtemperature
combinationsotherthanthoselisted.