Honeywell C7189U Stud Sensor User Manual


 
C7189U REMOTE INDOOR SENSOR
3 69-1710EFS-1
WIRING
The sensor can be used to provide one remote sensor (see Fig. 6) or as a temperature averaging network with multiple
sensors connected (see Fig. 7). The thermostat is not part of the average network.
CAUTION
ELECTRICAL HAZARD.
Can cause electrical shock or equipment damage. Disconnect power before wiring.
1. Run the wire cable from the thermostat to the
remote sensor location.
2. Loosen screw terminals, insert wires into terminal
block (polarity does not matter), then retighten
screws.
3. Push excess wire back into the wall opening.
4. Plug the wall opening with non-flammable insulation
to prevent drafts from affecting the sensor operation
and replace the cover on the remote sensor.
5. Connect the two wires to the thermostat's remote
sensor terminals (polarity does not matter) and
replace the thermostat back onto the wallplate. See
Fig. 6.
Fig. 5. Terminal block wiring.
Fig. 6. Wiring a single C7189U Sensor.
Fig. 7. Wiring Multiple C7189U Sensors.
OPERATION
Once a remote indoor temperature sensor is connected to
the thermostat, the thermostat's sensor is no longer used.
The thermostat's installer setup should be modified to tell
the thermostat that remote indoor temperature sensor(s)
have been used. The Inside temperature reading on the
thermostat's display will be the remote sensor(s)
temperature location(s). See Fig. 8.
.
Fig. 8. Inside Temperature Reading on TH8000 Series
Thermostat.
M24116
2
C7189
RC
R
W
Y
G
C
Y2
W2
S2
S1
M19972A
R
C
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
IF MORE THAN ONE C7189 REMOTE SENSOR IS REQUIRED,
REFER TO FIGURE 7.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
1
1
3
2
3
M19973
SENSORS MUST BE ARRANGED IN THIS
CONFIGURATION TO OPERATE CORRECTLY.
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
1
2
Y2
W2
S2
1
1
2
C7189
C7189
C7189 C7189
Y2
W2
2
1
1
2
C7189
C7189
C7189 C7189
C7189
C7189
C7189 C7189 C7189
Heat On
SCHED HOLD CLOCK SCREEN MORE
TUE
AM
FAN
AUTO
SYSTEM
HEAT
CHANGE FILTER UV LAMP HUMIDIFIER PAD
Following
Schedule
Inside
Set To
M19974