Honeywell CTS-20 Stud Sensor User Manual


 
SOLID CORE AND SPLIT CORE 4-20 MA OUTPUT CURRENT SENSORS
3 62-0245—01
aperture (hole) size of the current sensor is
3/4 in. (19 mm) and will accept a maximum cable
diameter of 350 MCM (17.3 mm).
Fig. 6. Wiring example
OPERATING SPECIFICATIONS
Max Sensing Current Voltage: 600 Vac
M23934
BUILDING AUTOMATION
SYSTEM
COMMON
+ 4-20 MA SIGNAL INPUT
GND (SHIELD)
+
+12-30 VDC
DC POWER SUPPLY
+
Table 1. Specifications by Product Number
Product Number
Core
Type Output Range Jumper
a
Max. Current
Continuous
Max. Current
for 6 secs.
CTS-20-005-AVG-001 Solid 4-20 mA Average 0-5 Amps Fixed None 100 Amps 125 Amps
CTS-20-050-AVG-001 Solid 4-20 mA Average 0-10 Amps
0-20 Amps
0-50 Amps
Low
Middle
High
100 Amps
150 Amps
200 Amps
125 Amps
225 Amps
300 Amps
CTS-20-250-AVG-001 Solid 4-20 mA Average 0-100 Amps
0-200 Amps
0-250 Amps
Low
Middle
High
200 Amps
360 Amps
400 Amps
250 Amps
450 Amps
500 Amps
CTS-20-005-VFD-001
b
Solid 4-20 mA True RMS 0-5 Amps Fixed None 60 Amps 100 Amps
CTS-20-050-VFD-001
b
Solid 4-20 mA True RMS 0-10 Amps
0-20 Amps
0-50 Amps
Low
Middle
High
60 Amps
100 Amps
160 Amps
80 Amps
200 Amps
300 Amps
CTS-20-250-VFD-001
b
Solid 4-20 mA True RMS 0-100 Amps
0-200 Amps
0-250 Amps
Low
Middle
High
160 Amps
320 Amps
400 Amps
200 Amps
400 Amps
500 Amps
CTP-20-005-AVG-001 Split 4-20 mA Average 0-5 Amps Fixed None 100 Amps 125 Amps
CTP-20-050-AVG-001 Split 4-20 mA Average 0-10 Amps
0-20 Amps
0-50 Amps
Low
Middle
High
100 Amps
150 Amps
200 Amps
125 Amps
225 Amps
300 Amps
CTP-20-200-AVG-001 Split 4-20 mA Average 0-100 Amps
0-150 Amps
0-200 Amps
Low
Middle
High
135 Amps
180 Amps
250 Amps
200 Amps
300 Amps
400 Amps
CTP-20-005-VFD-001
b
Split 4-20 mA True RMS 0-5 Amps Fixed None 60 Amps 100 Amps
CTP-20-050-VFD-001
b
Split 4-20 mA True RMS 0-10 Amps
0-20 Amps
0-50 Amps
Low
Middle
High
60 Amps
100 Amps
160 Amps
80 Amps
200 Amps
300 Amps
CTP-20-200-VFD-001
b
Split 4-20 mA True RMS 0-100 Amps
0-150 Amps
0-200 Amps
Low
Middle
High
135 Amps
180 Amps
250 Amps
200 Amps
300 Amps
400 Amps
a
All current sensors are shipped from the factory with the jumper set in the high range.
b
All VFD models have True RMS outputs and should be used with Variable Frequency Drives. Not CE compliant at
this time.