Honeywell G Stud Sensor User Manual


 
T7047C,G,H REMOTE SPACE SENSORS
3 62-0179
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Location
Locate the remote sensor about 5 ft (1.5m) above the
floor on an inside wall where it will be affected by freely
circulating air at average room temperatures.
Mounting
1. Loosen the cover locking screw with the Allen
wrench provided and remove the device cover.
2. Run wire to the selected location.
3. Thread wire through the semicircular hole in the
device.
4. Make connections to the T7047 (see the Wiring
section).
5. Select the proper screws for the application. Four
mounting screws are provided:
a. Two self-tapping type for wall mounting.
b. Two for outlet box mounting.
6. If air drafts occur through the wall opening,
eliminate with suitable material.
7. Fasten the T7047 on the wall or outlet box with
screws through the mounting holes in the device.
(See Fig. 2.)
8. Replace the cover and tighten the cover locking
screw.
Fig. 2. Mounting the T7047.
Fig. 3. T7047C1009 Remote Sensor resistance
change with change in temperature.
Fig. 4. T7047C1025 Remote Sensor resistance
change with change in temperature.
Fig. 5. T7047C1082 Remote Sensor resistance
change with change in temperature.
THERMOSTAT
MOUNTING
TAB SLOT (2)
WIRING
TERMINALS
M
OUNTING
T
AB (2 INSIDE
C
OVER)
COVER
M
OUNTING
S
CREW (2)
COVER LOCKING SCRE
W
OUTLET
BOX
M2007
2
2000
1800
1600
1400
1200
1000
10
20
30 40 50
60
70 80 90
100
RESISTANCE (OHMS)
1695 OHMS AT
75°F (24°C)
TEMPERATURE (DEGREES)
M339
9
-10
0 10
20 30 40
°
C
°
F
2
000
1
800
1
600
1
400
1
200
1
000
10
20
30 40 50
60
70 80 90
100
R
ESISTANCE
(
OHMS)
1420 OHMS AT
75 F (24 C)
TEMPERATURE (DEGREES)
M4034
-10
0 10
20 30 40
C
F
120K
100K
80K
60K
40K
20K
20
40
60 80 100
120
140 160 180
200
RESISTANCE (OHMS)
TEMPERATURE (DEGREES)
M339
8
0 10 20 30 40
F
220
C
-7 50 60 70 80 90 100
22,800 OHMS AT
77 F (25 C)