Philips T5VHO Work Light User Manual


 
LAMP
BALLAST
BLUE
YELLOW
BLACK/ORANGE
BLACK/WHITE
RED
(HOT)
(NEUTRAL )
Yellow leads must be connected for (1) lamp operation
Wiring Diagram–Lamp Operation
Advance JOP-2S95-G T5VHO for 2-lamp version ballast
Features
Programmed Start ballast
Ballast factor of 1.0 for 2-lamp version
277V–480V input voltage range, 50/60Hz
194˚F/90˚C maximum case temperature
-19˚F (-28˚C) minimum starting temperature
<10% Total Harmonic Distortion (THD)
One or two lamp operation
General Specifications
Section I—Physical Characteristics
1.1 The electronic ballast shall be furnished with integral leads color coded
to ANSI standard C82.11.
Section II—Performance Requirements
2.1 The electronic ballast shall be programmed start.
2.2 The electronic ballast shall operate from 250V–528V.
2.3 The electronic ballast shall maintain constant light output, for line
voltage variations of 10% of rated supply voltage.
2.4 The electronic ballast input current shall haveTotal Harmonic
Distortion (THD) of less than 10% at maximum light output
for primary lamps.
2.5 The electronic ballast shall have a Power Factor greater than 98%
at full light output.
2.6 The electronic ballast shall have a minimum ballast factor of 1.0
for primary lamp applications.
2.7 The electronic ballast lamp current crest factor shall be 1.7 or less
in accordance with lamp manufacturer recommendation.
2.8 The electronic ballast shall withstand a sustained open circuit and
output conditions without damage.
2.9 The electronic ballast shall be Sound Rated A.
2.10 The electronic ballast shall be a high frequency electronic type
and operate above 40 kHz to avoid interference with infrared
control systems, and eliminate visible flicker.
2.11The electronic ballast shall comply with ANSI C82.11, where applicable.
2.12 The electronic ballast shall provide transient immunity as specified
in ANSI C62.41.
2.13 The electronic ballast shall provide end of life protection circuitry.
2.14 The electronic ballast shall have a minimum starting temperature
of -19°F (-28°C) forT5VHO lamps.
Section III—Regulatory Requirements
3.1 The electronic ballast shall not contain any Polycholorinated
Biphenyl (PCB’s).
3.2 The electronic ballast shall be Underwriters Laboratories (UL 935)
listed, Class P and Type 1 Outdoor; and Canadian Standards
Association (CSA) certified, where applicable.
Section IV—Other
4.1 The manufacturer shall have a fifteen-year history of producing
electronic ballasts for the North American market.
4.2 The electronic ballast shall be produced in a factory certified
to ISO 9001 Quality System Standards.
Enclosure Dimensions
Advance JOP-2S95-G T5VHO Ballast
Advance 277V–480V (1) or (2) lamp 95W T5VHO Ballast
Ballast Ordering, Electrical and Technical Data
Lamp Maximum Min.
No. of Input Starting Ballast Catalog Input Power Ballast Line Current Starting
Lamps Volts Method Family Number ANSI (Watts) Factor (Amps) Temp(˚F/˚C)
1 277 PS Optanium JOP-2S95-G 116W 1.1 0.42A -19/-28
1 347 PS Optanium JOP-2S95-G 116W 1.1 0.35A -19/-28
1 480 PS Optanium JOP-2S95-G 116W 1.1 0.24A -19/-28
2 277 PS Optanium JOP-2S95-G 206W 1.0 0.74A -19/-28
2 347 PS Optanium JOP-2S95-G 206W 1.0 0.59A -19/-28
2 480 PS Optanium JOP-2S95-G 206W 1.0 0.43A -19/-28
Above specifications subject to change without notice.
LAMP
BALLAST
BLUE
YELLOW
BLACK/ORANGE
BLACK/WHITE
RED
(HOT)
(NEUTRAL )
LAMP
A . . . . . . . 1.18"
B . . . . . . . 1.70"
C . . . . . . 16.34"
D . . . . . . 16.70"
New P-5904-A T5 VHO Prod Bulletin.qxd:Layout 1 9/9/08 6:08 PM Page 3