EXTENSION CORD SELECTION
If an extension cord is used, make sure the conductor size is large enough to
prevent excessive voltage drop which will cause loss of power and possible motor
damage. A table of recommended extension cord sizes will be found in this
section. This table is based on limiting line voltage drop to 5 volts (10 volts for 230
volts) at 150% of rated amperes.
If an extension cord is to be used outdoors, it must be marked with the suffix W-
A or W following the cord type designation. For example – SJTW-A to indicate it
is acceptable for outdoor use.
RECOMMENDED EXTENSION CORD SIZES FOR USE WITH PORTABLE ELECTRIC TOOLS
Length of Cord in Feet
115V 25 Ft. 50 Ft. 100 Ft. 150 Ft. 200 Ft. 250 Ft. 300 Ft. 400 Ft. 500 Ft.
230V 50 Ft. 100 Ft. 200 Ft. 300 Ft. 400 Ft. 500 Ft. 600 Ft. 800 Ft. 1000 Ft.
0-2 18 18 18 16 16 14 14 12 12
2-3 18 18 16 14 14 12 12 10 10
3-4 18 18 16 14 12 12 10 10 8
4-5 18 18 14 12 12 10 10 8 8
5-6 18 16 14 12 10 10 8 8 6
6-8 18 16 12 10 10 8 6 6 6
8-10 18 14 12 10 8 8 6 6 4
10-12 16 14 10 8 8 6 6 4 4
12-14 16 12 10 8 6 6 6 4 2
14-16 16 12 10 8 6 6 4 4 2
16-18 14 12 8 8 6 4 4 2 2
18-20 14 12 8 6 6 4 4 2 2
Nameplate Ampere Rating
SAVE THESE INSTRUCTIONS!
MOTOR
Many Porter-Cable tools will operate on either D.C., or single phase 25 to 60 cycle
A.C. current and voltage within plus or minus 5 percent of that shown on the
specification plate on the tool. Several models, however, are designed for A.C.
current only. Refer to the specification plate on your tool for proper voltage and
current rating.
Do not operate your tool on a current on which the
voltage is not within correct limits. Do not operate tools rated A.C.
only on D.C. current. To do so may seriously damage the tool.