Tripp Lite 1250-3000 VA Welding System User Manual


 
7
Specifications
Storage & Service
Storage
Turn your UPS OFF: first, engage the ON/Standby Switch and release it to place
your UPS in the “Standby” mode; then set the System Enable Switch (Jumper #4,
UPS rear panel) to “DISABLE” (Down); finally, disconnect the UPS power cord
from the wall outlet. If you plan on storing your UPS for an extended period of
time, recharge the UPS batteries once every three months. Follow steps #1 and
#3 in the Installation section and allow the UPS to charge from 4 to 6 hours. If
you leave your UPS batteries discharged for an extended period of time, they will
suffer permanent loss of capacity.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the
ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter
describing the symptoms of the problem. If the UPS is within the 2 year warranty
period, enclose a copy of your sales receipt.
SMART 2200 NET SMART 3000 NET
Output Capacity (VA/Watts): 2200/1700 3000/2400
Battery Runtime (Half Load/Full Load) Minutes: 27+/11+ 23+/7+
Battery Recharge Rate: 2 - 4 hrs. 2 - 4 hrs.
Suggested Circuit: 15-amp or 20-amp dedicated 30-amp dedicated
Approvals: UL, cUL UL, cUL
SMART 1250XL NET SMART 2200XL NET
Output Capacity (VA/Watts): 1250/900 2200/1750
Battery Runtime (Half Load/Full Load) Minutes: 85+/24+ 28+/11+
Battery Recharge Rate: 2 - 4 hrs. 2 - 4 hrs.
Suggested Circuit: 15-amp 20-amp dedicated
Approvals: UL, cUL UL, cUL
ALL MODELS:
Input Voltage/Frequency (120V/60 Hz); On Line Input Voltage Range (87 - 140 volts); Voltage-Regulated Output Voltage Range
(120V +/- 9%); On Battery Output Voltage Range (120V +/- 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform
Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB);
AC Protection Modes (H to N, H to G, N to G).
9811198 SmartPro NET & SmartPro XC Owners Manual.p65 5/17/00, 10:57 AM7