Troy-Bilt 01919-1 Welding System User Manual


 
10
Section 4: Operation
RECEPTACLES
120/240 Volt AC, 30 Amp, Locking
Receptacle
Use a NEMA L14–30 plug with this receptacle. Connect a
4–wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 5).You can use the same 4–wire cord if you
plan to run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 5,550 watts of power
(5.55 kW) at 23.1 Amps for 120 Volts or 240 Volts.The
outlet is protected by a push–to–reset circuit breaker.
120 Volt AC, 20 Amp, Duplex
Receptacles
Each duplex receptacle (Figure 6) is protected against
overload by a push–to–reset circuit breaker.
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
GENERATOR ADAPTER
CORD SET
The generator is equipped with a 25’ generator adapter cord
set designed for a 240 Volt, 30 Amp grounded neutral circuit
(Figure 7).The generator adapter cord set provides a
convenient supply of emergency power into your dwelling so
that your generator can be operated safely outside.
The maximum load on each outlet is 20 Amps.The
maximum total load on both yellow wire outlets or black
wire outlets is 30 Amps.
NOTE: Follow all safety precautions when connecting any
extension cord or device to the generator.
Figure 7 — Generator Adapter Cord Set
Figure 6 — 120 Volt, 20 Amp Duplex Receptacle
Figure 5 — 120/240 Volt AC, 30 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-30
Ground (Green)
NEVER attempt to power a device requiring more amperage
than generator or receptacle can supply.
DO NOT overload the generator. See “Don’t Overload
Generator”.
Receptacles may be marked with rating value greater
than generator output capacity.
CAUTION