Troubleshooting Reference
No output voltage. The Status LED is green
or yellow.
GFCI has tripped or 15A supplementary
breaker has tripped.
Circuit breaker on the AC load panel or
AC output disconnect has tripped.
Battery voltage is too low (depending
on setting, see “Operating Limits” on
page 21) to start inverting. Display
screen may show DC voltage as ..
Check load and reset the GFCI or supplementary breaker.
Reset the circuit breaker or check the AC output disconnect
circuits.
Check DC connections and cable.
Recharge battery.
No output voltage. The status LED is not
lighting up.
AC shore power is not available or out
of operating range and the inverter is
OFF.
Check AC shore power.
Turn the inverter ON.
AC shore power is not available and the
inverter is OFF due to a shutdown for
more than 30 seconds.
Check AC shore power and battery voltage.
Turn the inverter ON and look at the display panel for any
error code.
See Table 1, “Error Codes Displayed on the Display Panel
Screen” on page 33.
The inverter’s DC input polarity is
reversed.
The inverter was probably damaged due to the reverse polarity.
This type of damage is NOT covered by the warranty.
Return the unit.
See Warranty Card for information on returning the unit.
Table 2
Troubleshooting Reference
Problem Possible Cause Solution