Command Set 5017H/5017UH
Analog Input
$aaSiCjB
Example command: $35S3C1B(cr)
response: !350b00(cr)
Channel 1 of the ADAM-5017H / 5017UH module in
slot 3 of the ADAM-5000 system at address 35h
responds with an input range 0-20 mA, engineering unit
data format.