D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
12 Bosch Security Systems, Inc. | 8/06 | F01U011791B
4.4.5 Keypad (Command Center) Functions
The following keypad function must be enabled or
passcode required to enable the [DETECTOR RESET]
key.
• #27 Reset Sensors
Include the following items in the menu:
• #9 View Event Memory
• #10 View Point Status
• #12 Fire Test
• #21 View Log
• #29 Remote Program
• #32 Display Rev
Refer to Figure 18.
For the D9412GV2 Control Panel, program
each of the keypad functions with E
(enabled) and not P (passcode required). If
restricting any of the keypad functions with
a passcode is required, those functions
must be executed from a custom function
that includes an authorized passcode.
Example (Refer to Figure 18.): If the
keypad function View Memory is
programmed as P (passcode required), and
the passcode 125600 has authority to
execute it, the keystrokes would be:
[A] [4] [0] [1] [2] [5] [6] [0] [0] [E]
When creating a Menu Function List for a
keypad address, consider that the
D1256RB Keypad does not have numeric
keys. Ensure that:
• no passcode-protected keypad functions
are in a Menu Function List enabled at
an address that coincides with the
installed address for a D1256RB
Keypad.
• the
CC# Menu Key Lock
prompt is set
to No for the D1256RB address.
Figure 18: Example – Keypad Functions
Keypad Functions
# Functions Command
E/P*
1 Disarm ?
2 Master Arm Delay ? CMD 1
3 Master Arm Instant ? CMD 11
4 Perimeter Instant ? CMD 2
5 Perimeter Delay ? CMD 3
6 Watch Mode ? CMD 6
E
7 Perimeter Part ? CMD 8
8 View Area Status ?
9 View Memory ? CMD 40
E
10 View Pt Status ?
E
11 Walk Test ? CMD 44
E
12 Fire Test ? CMD 58
13 Send Report ? CMD 41/42
14 Door Control ? CMD 46
Cycle Door ?
E
Unlock Door ?
E
Secure Door ?
E
37 Access Control Level?
15 Change Display ? CMD 49
E
16 Change Time/Date ? CMD 45
E
17 Change Passcode ? CMD 55
18 Add User ? CMD 56
19 Del User ? CMD 53
20 Extend Close ? CMD 51
21 View Log ?
E
22 Print Log ?
23 User Command 7 ? CMD 7
24 User Command 9 ? CMD 9
25 Bypass a Point ? CMD 0
26 Unbypass a Point ? CMD 00
27 Reset Sensors ? CMD 47
E
28 Change Relays ? CMD 54
29 Remote Program ? CMD 43
30 Move To Area ? CMD 50
32 Display Rev ? CMD 59
E
33 Service Walk ?
34 Default Text ? CMD 57
35 Change Skeds ? CMD 52
36 Invisible Walk ?
* Keypad Function options: P = Passcode;
E = Enabled (no passcode required);