![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/4/00/400a4665-4d6e-49a1-85d8-9d3b9a246451/400a4665-4d6e-49a1-85d8-9d3b9a246451-bga1.png)
161
Fan Performance — 48PMD24 — Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
F
937 3.26
F
988 3.56
F
1036 3.53
F
1083 3.90
G
1127 4.28
6000
1013 3.58 1060 3.96 1105 4.35
G
1149 4.75
1191 5.16
6500
1089 4.48
G
1133 4.89
G
1175 5.31 1216 5.73
H
1256 6.17
7000 G
1166 5.52
H
1207 5.96
H
1247 6.41
H
1285 6.86 1323 7.32
7500
H
1243 6.71 1282 7.18 1319 7.66 1355 8.14 1391 8.63
8000
1320 8.07 1356 8.57 1392 9.08 — — — —
8500
1398 9.60 — — — — — — — —
9000
— — — — — — — — — —
9500
— — — — — — — — — —
10000
— — — — — — — — — —
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
G
1171 4.67
G
1212 5.06
G
1253 5.47
H
1292 5.88
H
1331 6.30
6000
1232 5.57
H
1271 6.00
H
1310 6.43 1348 6.87 1384 7.31
6500 H
1295 6.61 1333 7.06 1369 7.52 — — — —
7000
1360 7.80 1396 8.27 — — — — — —
7500
— — — — — — — — — —
8000
— — — — — — — — — —
8500
— — — — — — — — — —
9000
— — — — — — — — — —
9500
— — — — — — — — — —
10000
— — — — — — — — — —
LEGEND
Bhp - Brake Horsepower Input to Fan
Boldface indicates field-supplied drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid‐Low Range: 896 to 1227 rpm, 4.26 Bhp (208/230 and 460‐v), 873 to 1108
rpm, 5.75 Bhp (575‐v)
(G) Mid‐High Range: 1113 to 1414 rpm, 5.75 Bhp
(H) High Range: 1096 to 1339 rpm, 8.63 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
Fan Performance — 48PME24 — Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
F
952 3.38
F
1003 3.32
F
1053 3.70
F
1100 4.09
G
1145 4.49
6000
1029 3.74 1077 4.15
G
1123 4.56
G
1167 4.98
1210 5.41
6500
1106 4.67
G
1151 5.11 1194 5.56
H
1236 6.01
H
1276 6.47
7000
G
1184 5.75
H
1226 6.23
H
1266 6.71 1306 7.19 1344 7.68
7500
H
1262 7.00 1302 7.50 1340 8.01 1377 8.53 — —
8000
1341 8.41 1378 8.95 — — — — — —
8500
— — — — — — — — — —
9000
— — — — — — — — — —
9500
— — — — — — — — — —
10000
— — — — — — — — — —
Airflow
(Cfm)
Available External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
5500
G
1189 4.90
G
1232 5.31
G
1273 5.72
H
1313 6.15 1352 6.58
6000
H
1251 5.85
H
1292 6.29
H
1331 6.74 1369 7.19 — —
6500
1315 6.94 1354 7.41 1391 7.89 — — — —
7000
1381 8.18 — — — — — — — —
7500
— — — — — — — — — —
8000
— — — — — — — — — —
8500
— — — — — — — — — —
9000
— — — — — — — — — —
9500
— — — — — — — — — —
10000
— — — — — — — — — —
LEGEND
Bhp - Brake Horsepower Input to Fan
Boldface indicates field-supplied drive required.
NOTES:
1. Motor drive ranges:
(E) Low Range: Not Used
(F) Mid‐Low Range: 896 to 1227 rpm, 4.26 Bhp (208/230 and 460‐v), 873 to 1108 rpm,
5.75 Bhp (575‐v)
(G) Mid‐High Range: 1113 to 1414 rpm, 5.75 Bhp
(H) High Range: 1096 to 1339 rpm, 8.63 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
48/50PG and PM