37
Table 31 — Service Test
ITEM EXPANSION RANGE UNITS POINT WRITE STATUS
TEST Service Test Mode ON/OFF MAN_CTRL
STOP Local Machine Disable YES/NO UNITSTOP config
S.STP Soft Stop Request YES/NO SOFTSTOP forcible
FAN.F Supply Fan Request YES/NO SFANFORC forcible
INDP TEST INDEPENDENT OUTPUTS
→HUM.R Humidifier Relay ON/OFF HUMR_TST
→ALRM Remote Alarm/Aux Relay ON/OFF ALRM_TST
FANS TEST FANS
→F.MOD Fan Test Automatic? YES/NO FANAUTO
→E.POS Econo Damper Command Pos % ECONFANS
→S.FAN Supply Fan Relay ON/OFF SFAN_TST
→I.POS IGV Actuator Command Pos 0-100 % IGVFNTST
→S.VFD Supply Fan VFD Speed 0-100 % SGVFDTST
→P.E. 1 Power Exhaust Relay 1 ON/OFF PE1_TST
→P.E. 2 Power Exhaust Relay 2 ON/OFF PE2_TST
→BP1.P BP 1 Command Position 0-100 % BLDPTST1
→BP2.P BP 2 Command Position 0-100 % BLDPTST2
→E.VFD Exhaust Fan VFD Speed 0-100 % EFVFDTST
→CD.F.A Condenser Fan Circuit A ON/OFF CNDA_TST
→CD.F.B Condenser Fan Circuit B ON/OFF CNDB_TST
→CD.MM Motormaster Condenser Fan ON/OFF PCFABTST
ACT.C CALIBRATE TEST-ACTUATORS
→ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOTST
→E.CAL Economizer Calibrate Cmd YES/NO ECONOCAL
→ECN.A Econ Act. Control Angle read only ECONCANG
→EC2.C Economzr 2 Act.Cmd.Pos. 0-100 % ECON2TST
→E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL
→EC2.A Econ2 Act.Control Angle read only ECN2CANG
→IGV.C IGV Actuator Command Pos 0-100 % SPIGVTST
→I.CAL IGV Act. Calibrate Cnd YES/NO IGV_CAL
→IGV.A IGV Act. Control Angle read only IGC_CANG
→IGV.M VFD-IGV Maximum Speed 0-100 % STATPMAX
→BP1.C BP 1 Command Position 0-100 % BLDG1TST
→B1.CL BP 1 Actuator Cal Cmd YES/NO BLDG1CAL
→BP1.A BP Act.1 Control Angle read only BP1_CANG
→BP1.M
BP 1 Actuator Max Pos. 0-100 % BP1SETMX
→BP2.C BP 2 Command Position 0-100 % BLDG2TST
→B2.CL BP 2 Actuator Cal Cmd YES/NO BLDG2CAL
→BP2.A BP Act.2 Control Angle read only BP2_CANG
→BP2.M BP 2 Actuator Max Pos. 0-100 % BP2SETMX
→HTC.C Ht.Coil Command Position 0-100 % HTCLACTC
→HT.CL Heating Coil Act. Cal.Cmd YES/NO HCOILCAL
→HTC.A Heat Coil Act.Ctl.Angle read only HTCLCANG
→HMD.C Humidifier Command Pos. 0-100 % HUMD_TST
→HM.CL Humidifier Act. Cal.Cmd YES/NO HUMIDCAL
→HMD.A Humidifier Act.Ctrl.Ang. read only HUMDCANG
COOL TEST COOLING
→E.POS Econo Damper Command Pos 0-100 % ECONCOOL
→SP.SP Static Pressure Setpoint 0-5 "H2O SPSP_TST
→CL.ST Requested Cool Stage 0-n CLST_TST
→LD.LG Lead/Lag Select Test LEAD/LAG LL_TST
→A1 Compressor A1 Relay ON/OFF CMPA1TST
→U1.A1 Unloader 1 - Comp A1 ON/OFF UNL1_TST
→U2.A1 Unloader 2 - Comp A1 ON/OFF UNL2_TST
→A2 Compressor A2 Relay ON/OFF CMPA2TST
→B1 Compressor B1 Relay ON/OFF CMPB1TST
→U1.B1 Unloader 1 - Comp B1 ON/OFF UNL3_TST
→U2.B1 Unloader 2 - Comp B1 ON/OFF UNL4_TST
→B2 Compressor B2 Relay ON/OFF CMPB2TST
HEAT TEST HEATING
→HT.ST Requested Heat Stage 0-n HTST_TST
→HT.1 Heat Relay 1 ON/OFF HS1_TST
→HT.2 Heat Relay 2 ON/OFF HS2_TST
→HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST
→HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST
→HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST
→HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST
→H.I.R Heat Interlock Relay ON/OFF HIR_TST
→HTC.C Ht.Coil Command Position 0-100 % HTCLHEAT