A SERVICE OF

logo

When Units Are Interconnected
Only the red LED of the alarm “which senses the smoke” or
“is being tested” (the originating unit) will flash rapidly. All
other units in the interconnect system will sound an alarm
but their red LED’s will NOT flash rapidly.
Testing
Test by pushing the Test button on the cover and hold
it down for a minimum of 5 seconds. This will sound
the alarm if all the electronic circuitry, horn and battery
are working. In an interconnected installation all
interconnected alarms should sound when the test button
on any one of the interconnected alarms is pressed. If
no alarm sounds, the unit has defective batteries or other
failure. DO NOT use an open flame to test your alarm,
you could damage the alarm or ignite combustible
materials and start a structure fire.
Alarm Memory
This smoke alarm is equipped with an alarm memory
feature which produces a visual indication when an alarm
has been activated. A lit red LED indicates the memory
condition. The memory will remain activated until it is
reset by pushing the test button.
Test the alarm weekly to ensure proper operation. Erratic
or low sound coming from your alarm may indicate a
defective alarm, and it should be returned to place of
purchase (see Warranty section).
NOTE: WEEKLY TESTING IS REQUIRED!
Operation
16