A SERVICE OF

logo

PAGE 6 — DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10)
SPECIFICATIONS
Table 1. Generator Specifications
Model DCA-180SSJU
Type
Revolving field, self ventilated, open protected type synchronous
generator
Armature Connection
Star with Nutreal
Phase
3
Standby Output
198 KVA (158 KW)
Prime Output
180 KVA (144 KW)
Voltage
240V or 480V
Frequency
60 Hz
Speed
1800 rpm
Power Factor
0.8
Aux. AC Power
Single Phase, 60 Hz
Voltage
120 V
Output
4.8 KW (2.4 KW x 2)
Weight (No Fuel)
6,571 lbs. (2,980 kg.)
Weight (With Fuel)
7,489 lbs. (3,400 kg.)
Engine Specifications
Model
JOHN DEERE 6068HF485
Type
4 Cycle, water-cooled, direct injection, turbo-charged,
air to air intercooled
No. of Cylinders
6 cylinders
Bore x Stroke
4.17 in. x 5 in. (106 mm x 127 mm)
Rated Output
286 HP/1800 rpm
Displacement
415 cu. in. (6.8 liters)
Starting
Electric
Fuel Tank Capacity
100 gal. (380 liters)
Coolant Capacity
6.34 gal. (24 liters)
Lube Oil Capacity
8.69 gal. (32.9 liters)
Fuel Consumption
11.4 gal. (43 L)/hr at full load 9.0 gal. (34.1 L)/hr at 3/4 load
6.6 gal. (25.1 L)/hr at 1/2 load 4.3 gal. (16.2 L)/hr at 1/4 load
Battery
12V 128 Ah
Fuel
#2 Diesel Fuel