GENERATOR SHUT-DOWN PROCEDURES

1. Place the  circuit breakers (Figure
50) in the OFF position.
2. Turn the ignition key (Figure 52) to the STOP position.
Figure 52. Ingition Switch (Emergency)

To shutdown the generator, use the following procedure:
1. Place both the  circuit breakers
as shown in Figure 50 to the OFF position..
Figure 50. Main, GFCI and Load
Circuit Breakers Off
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the ignition switch (Figure 51) in the “STOP
position, remove the key and store in a safe place.
Figure 51. Ingition (Switch Normal)
4. Verify that all status LEDs on the MPEC display are
OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
WARNING
 stop the engine suddenly except in an
emergency.