![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/5/ff/5ffafca7-88e5-4299-86ec-5204291d65eb/5ffafca7-88e5-4299-86ec-5204291d65eb-bg24.png)
GENERATOR START-UP PROCEDURE (AUTO MODE)
Before connecting this generator to any
building’s electrical system, a licensed
electrician must install an isolation
Serious damage to
the building’s electrical system may occur without this
transfer switch.
When connecting the generator to a isolation (transfer)
switch, have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
When running the generator in the mode,
remember the generator can start up at any time without
warning. attempt to perform any maintenance
when the generator is in the auto mode.
The engine speed switch must be set to the “High”
position when running in the mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the generator is set in the mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
NOTICE
When the MPEC control switch is placed in the
position, the engine glow plugs will be warmed and the
engine will start automatically.
When starting generator in mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the engine speed switch (Figure 51) in the
position
Figure 51. Engine Speed Switch (High)
3. Place the (Figure 52) in the
position.
Figure 52. MPEC Control Switch (AUTO)
4. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 5).