Overview
The 10-175UL is a power limited power supply/charger that will convert 115VAC / 60Hz
input, into two individually PTC protected 12VDC or 24VDC output, (see specifications).
They are intended for use in applications requiring UL Listing for Access Control (UL294)
and applications requiring an interface with Fire Alarm Control Panels. It must be installed
in accordance with National and Local Electrical Codes and Regulations.
Specifications
• UL listed Access Control (UL294)
• CSFM approved - California State Fire Marshal
• MEA approved - NYC Dept. of Buildings 18-98-E
• NFPA 101 (Life Safety)
• Input 115VAC/60 Hz, .6 amps
• Switch selectable 12VDC or 24VDC power limited output
• 1.75 amps continuous supply current @ 12VDC or 24VDC
• Latching fire alarm tie-in with manual reset
• Filtered and electronically regulated output
• Charge current: 0.4 amps Max
• Aux relay output: (form “C”, 1 amp, 28VDC)
• AC Fail output relay (form “C” 1 amp, 28VDC)
• Enclosure Dimensions: 15.5”H x 12”W x 4.5”D
Output Specifications
Output VDC Switch Position Max. Stand-by Max. Alarm Battery
Load DC Load DC (Optional)
12VDC SW1 Open 1.75 amps 1.75 amps 12VDC
24VDC SW1 Open 1.75 amps 1.75amps 24VDC
Stand-By Specifications
Output 4Hr. of Stand-by & 5 minutes of alarm
12VDC / 7 AH Battery Stand-by = 1.25 amps
24VDC / 7 AH Battery Alarm = 1.25 amps
2