44 Xanbus Automatic Generator Start (AGS) Owner’s Guide
Configuration of the Xanbus AGS
Cfg Trigger
The "Cfg Trigger" menu contains the settings for automatically starting
and stopping the generator. This menu allows the adjustment of the default
settings for battery voltage, thermostat ON/OFF signals, inverter load, and
battery charging stage.
There are three classes of triggers: charger-based, thermostat-based, and
inverter load-based. If the generator is started by a trigger in one class, a
stop condition must also be set in order for the generator to stop. For
example for charger triggers, if the generator is started by the "Start DCV
30 sec" condition, any of the accompanying stop triggers "Stop Float",
"Stop Float" and "Stop V" can be used to stop it.
If at least one start trigger is enabled in two or all three trigger classes, the
first trigger to be true will start the generator. Conversely, the last stop
trigger to be met will stop the generator.
Changing the default settings is advised for experienced users or users who
have consulted service personnel.
The "Cfg Trigger" menu contains the following items:
Charger Triggers:
"Start DCV 30 sec"
"Start DCV 15 min"
"Start DCV 2 hr"
"Start DCV 24 hr"
"Stop Float"
"Stop Absorb"
"Stop V"
Thermostat Triggers:
"Temp1"
"Temp2"
Inverter Load Triggers:
"Load"
"Start Load"
"Stop Load"
IMPORTANT:
The Auto Gen Start mode must be set to Manual Off before
any start trigger parameters are set.