APC 240V Battery Charger User Manual


 
Symmetra
LX
Start-Up Guide
Extended Run Cabinets
For use with Symmetra LX UPS models:
990-1873-001 04/2005
®
200V, 4–8 kVA
208/240V, 4–8 kVA
220/230/240V, 4–8 kVA
200V, 4–16 kVA
208/240V, 4–16 kVA
220/230/240V, 4–16 kVA
READ FIRST
Important Safety and Installation Instructions
This guide is applicable for the Symmetra LX tower and rack-mount
extended run cabinet models. These units provide extended run time for the
Symmetra LX tower or rack-mount UPS models.
See and retain the product documentation shipped with your system for
other important installation, operation, and maintenance instructions.
Illustrations are representative. The Symmetra LX configuration, including
components and optional APC equipment, may be different from the models
shown in this guide.
Entire contents copyright 2005 by American Power Conversion Corporation.
All rights reserved. Reproduction in whole or in part without permission is
prohibited.
APC, the APC logo, InfraStruXure, PowerChute, Smart-UPS and Symmetra
are registered trademarks of American Power Conversion Corporation. All
other trademarks are the property of their respective owners.
9-Battery
Rack-mount
Extended Run
9-Battery
Tower
Extended Run
3-Battery
Rack-mount
Extended Run
Overview
1. Read Safety and General Information Instructions
2. Refer to the UPS Documentation
If installing the Symmetra LX and the Extended Run Cabinet(s),
install according to the instructions in the Symmetra LX Start-Up
Guide shipped with the UPS.
3. Install the Extended Run Cabinet(s)
Perform the physical installation for the extended run cabinet(s).
See the included Symmetra LX Physical Installation Guide.
4. Follow the proceeding Start-Up Instructions
See these instructions once the physical installation for the
Extended Run Cabinet(s) is complete. This section contains
information on how to connect, test, and start the unit.
Electrical
Hazard
Read, understand and follow ALL safety
instructions contained in the Symmetra LX Safety
Instructions and General Information Guide.
Failure to follow safety instructions and warnings
could result in equipment damage, serious injury,
or death.
Start-Up Instructions
1. Connect the first Extended Run Cabinet
1.1 Remove the screw and battery connector cover from the
back of the UPS.
1.2 Connect the power cable of the first extended run cabinet
to the UPS battery connector .
1.3 Set the dial of the extended run cabinet to ‘2’.
1.4 Connect the communications cable from the extended run
communications connector on the UPS to the connector on
the extended run cabinet .
Note
The illustrations shown in this section are applicable for the
tower and rack-mount extended run cabinets.
Note
If connecting to a UPS with integrated extended run, set the
dial of the first extended run cabinet to ‘3’ instead of ‘2’.