SECTION 2: CIRCUIT REQUIREMENTS
Circuit Requirements
Serious personal injury could occur if you
connect the machine to the power source
before you have completed the set up pro
-
cess. DO NOT connect the machine to the
power source until instructed to do so.
Full Load Amperage Draw
G0637 7
1
2 HP 220V 3-Phase ...............25 Amps
G0637 7
1
2 HP 440V 3-Phase ............12.5 Amps
G0638 10 HP 220V 3-Phase .................30 Amps
G0638 10 HP 440V 3-Phase .................15 Amps
Circuit Requirements
We recommend connecting your machine to a
dedicated and grounded circuit that is rated for
the amperage given below. Never replace a circuit
breaker on an existing circuit with one of higher
amperage without consulting a qualified electri
-
cian to ensure compliance with wiring codes
. If
you are unsure about the wiring codes in your
area or you plan to connect your machine to a
shared circuit, consult a qualified electrician.
G0637 7
1
2 HP 220V 3-Phase .................40 Amp
G0637 7
1
2 HP 440V 3-Phase .................20 Amp
G0638 10 HP 220V 3-Phase ...................40 Amp
G0638 10 HP 440V 3-Phase ...................20 Amp
Connection to Power
Have a qualified electrician hardwire this machine
to a dedicated locking shut-off switch (see Figure
2) that is connected to the main power source.






Figure 2. Hardwired locking disconnect switch.
Electrocution or fire could
result if this machine is
not grounded correctly
or if your electrical con
-
figuration does not com
-
ply with local and state
codes. Ensure compliance
by checking with a quali
-
fied electrician!
When using a phase converter, the power from
the manufactured power leg (sometimes called
the wild wire) can fluctuate. Connect the manu
-
factured power leg to the 3L/2 terminal to prevent
damage to the IC board or transformer. The wire
from this terminal can handle some fluctuation
because it goes directly to the motor. The power
going to the 1L/2 and 5L/3 terminals goes to the
IC board and transformer and must be consistent
to prevent damage.
Phase Converter