26
C076 Communication error select
• 00 Trip (error code E60)
• 01 Decelerate to stop and trip (error code E60)
• 02 Disable
• 03 Free run stop (coasting)
• 04 Decelerate to a stop
02
C077 Communication error time-out 0.00
C078 Communication wait time 0.
C081 O input span calibration 100.0
C082 OI input span calibration 100.0
C085 Thermistor input tuning 100.0
C086 [AM] terminal offset tuning 0.0
C091 Debug mode enable
• 00 Display • 01 No display
00
C101 Up/Down memory mode selection
• 00 Clear last frequency (return to default
frequency F001)
• 01 Keep last frequency adjusted by UP/DWN
00
C102 Reset selection
• 00 Cancel trip state at input signal ON transi-
tion, stops inverter if in Run Mode
• 01 Cancel trip state at signal OFF transition,
stops inverter if in Run Mode
• 02 Cancel trip state at input signal ON transi-
tion, no effect if in Run Mode
00
C141 Input A select for logic
output
Nine option codes
available
(LOG excluded),
see page 29
00
C142 Input B select for logic
output
01
C143 Logic function select
• 00 [LOG] = A AND B
• 01 [LOG] = A OR B
• 02 [LOG] = A XOR B
00
C144 Terminal [11] ON delay 0.0
C145 Terminal [11] OFF delay 0.0
C146 Terminal [12] ON delay 0.0
C147 Terminal [12] OFF delay 0.0
C148 Output relay ON delay 0.0
C149 Output relay OFF delay 0.0