OM-4418 Page 24
SECTION 7 − OPERATING AUXILIARY EQUIPMENT
. The welding generator provides power while welding and with the Amperage control in any position. However, under these conditions equipment
connected to the welding generator may be subject to larger than normal voltage fluctuations. It is recommended that only lamps be powered under
these conditions.
7-1. Generator Power Panel Receptacles
! Use GFCI-protected extension
cord.
. Generator power decreases as weld
current increases.
Set Amperage control at max. for full
generator power.
1 240 V 20 A AC Duplex Receptacle
RC1
RC1 supplies 60 Hz single-phase power at
weld/power speed. Maximum output is 4
kVA/kW.
2 120 V 20 A AC Duplex Receptacle
RC2
RC2 supplies 60 Hz single-phase power at
weld/power speed. Maximum output from
RC2 is 2.4 kVA/kW.
3 Supplementary Protector CB1
CB1 protects the receptacles from over-
load. If CB1 opens, the receptacles do not
work.
. Place switch in the On position to re-
set. If supplementary protector contin-
ues to open, contact Factory
Authorized Service Agent.
Combined output of all receptacles limited
to 4 kVA/kW rating of the generator (See
Section 11 − Generator Power Guide-
lines).
EXAMPLE: If 15 A is drawn from the 120
volt duplex receptacle, only 9 A is available
from the 240 V duplex receptacle.
(120 V x 15 A) + (240 V x 9 A) = 4 kVA/KW.
226 005
21
3