3-5. Electrical Service Guide
Y CAUTION: INCORRECT INPUT POWER can damage this welding power source. This welding pow-
er source requires a CONTINUOUS supply of 60 Hz (+10%) power at +10% of rated input voltage. Do
not use a generator with automatic idle device (that idles engine when no load is sensed) to supply
input power to this welding power source.
Actual input voltage should not exceed ± 10% of indicated required input voltage. If
actual input voltage is outside of this range, output may not be available.
NOTE
60 Hz Three Phase
60 Hz Single
Phase
Input Voltage 230 460 575 230 460
Input Amperes At Rated Output 31 15 12 53 27
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
35 15 15 60 30
Normal Operating 3 45 20 20 80 40
Min Input Conductor Size In AWG/Kcmil 10 14 14 8 10
Max Recommended Input Conductor Length In Feet (Meters)
112
(34)
175
(53)
274
(83)
85
(26)
224
(68)
Min Grounding Conductor Size In AWG/Kcmil 10 14 14 8 10
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 Time-Delay fuses are UL class RK5 .
3 Normal Operating (general purpose - no intentional delay) fuses are UL class K5 (up to and including 60 amp), and UL class H ( 65 amp and
above).