Hobart Champion 4500 Air Compressor User Manual


 
OM-4418 Page 17
SECTION 6 – OPERATING AUXILIARY EQUIPMENT
The welding generator provides power while welding and with the Current control
in any position. However, under these conditions equipment connected to the
welding generator may be subject to larger than normal voltage fluctuations. It is
recommended that only lamps be powered under these conditions.
NOTE
6-1. Generator Power Panel Receptacles
Y Use GFCI-protected extension
cord.
. Generator power decreases as weld
current increases.
Set Amperage control at max. for full
generator power.
1 240 V 20 A AC Duplex Receptacle
RC1
RC1 supplies 60 Hz single-phase power at
weld/power speed. Maximum output is 4
kVA/kW.
2 120 V 20 A AC Duplex Receptacle
RC2
RC2 supplies 60 Hz single-phase power at
weld/power speed. Maximum output from
RC2 is 2.4 kVA/kW.
3 Circuit Breaker CB1
CB1 protects the receptacles from over-
load. If CB1 opens, the receptacles do not
work.
. Place switch in the On position to reset
circuit breaker. If breaker continues to
open, contact Factory Authorized Ser-
vice Agent.
Combined output of all receptacles limited
to 4 kVA/kW rating of the generator (See
Section 10 – Generator Power Guide-
lines).
EXAMPLE: If 15 A is drawn from the 120
volt duplex receptacle, only 9 A is available
from the 240 V duplex receptacle.
(120 V x 15 A) + (240 V x 9 A) = 4 kVA/KW.