Honeywell DR65 Tool Storage User Manual


 
Specications
Install TrueDRY DR65 according to National Electric Codes.
Dimensions in inches and (mm):
Product weight: 55 lb (25 kg)
Shipping weight: 65 lb (30 kg)
Shipping dimensions: 16 in. H x 15 in. W x 31 in. L
Media Filter: MERV 11, 9 in. H x 11 in. W x 1 in. D
Drain connection: 3/4-in. threaded female NPT
connection, with attached 3/4-in. male connection.
Duct connections: 8-in. round inlet and outlet. ABS
plastic, compatible for connection to rigid or
flexible ducting with sheet metal screws and/or
tape.
Cabinet:20gaugegalvanizedsteelpowder-coat
painted.
Insulation: R value 1
Compressor: Rotary-style, 5.8 KBTU
Refrigerant:R-410A,15oz.
Operating Temp Range (outside cabinet):
34ºF to 135ºF (1.1ºC to 57.2ºC)
Operating Humidity Range: 0-99% RH
Input ratings
•Electricalinputvoltage:120VAC,60Hz
nominal
•Inputcurrent:5.2A
Output ratings
•Power transformer to R/C terminals: 24
VAC, 0.85 A
•Energy Performance: 2.22 liters (4.7 pints)
per kilowatt hour (KWH)
Standards and approval body require-
ments
ETL Tested per standard UL 474 ducted
dehumidifier.
ENERGY STAR rated.
Dry-Bulb Temp Intake Humidity Capacity (Pints/Day)
80°F (26.7°C) 60% RH 65
70°F (21.1°C) 60% RH 42
60°F (15.6°C) 60% RH 21
Home Size
(square ft)
Dehumidifier Capacity Required to Maintain Desired Indoor RH*
60% RH Indoor
(pints/day)
50% RH Indoor
(pints/day)
40% RH Indoor
(pints/day)
2080 49–54 55–58 71–78
2600 61–68 65–72 90–97
3120 75–82 79–86 95–110
* Based on extreme climates where outdoor humidity is 70-90% RH. For less extreme climates, larger
homes can be adequately served with less capacity. Actual requirements may vary.
Airflow versus external static pressure
(0–1 in. water pressure) with collars
attached
0 in. 160 CFM
0.2 in. 140 CFM
0.4 in. 120 CFM
0.6 in. 100 CFM
M29763
28-1/2 (724)
12 (305)
12
(305)
8 INCH (203)
DIAMETER
TrueDry DR65 Dehumidication System 69-2089EFS—11
4