Lincoln Electric 10,000 PLUS Welder User Manual


 
240 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
40 AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
A-9
INSTALLATION
RANGER 10,000 PLUS AND RANGER 10,000
A-9
Connection of RANGER 10,000 PLUS OR RANGER
10,000 to premises wiring must be done by a
licensed electrician and must comply with the
National Electrical Code and all other applicable
electrical codes.
Figure 1
CONNECTION OF RANGER 10,000 PLUS OR RANGER 10,000 TO PREMISES WIRING