Lincoln Electric 11389 Welder User Manual


 
WELD CABLE SIZE
Table A.1 located below are copper cable sizes rec-
ommended for different currents and duty cycles.
Lengths stipulated are the distance from the welder to
work and back to the welder again. Cable sizes are
increased for greater lengths primarily for the purpose
of minimizing cable drop.
** Tabled values are for operation at ambient temperatures of 104°F(40°C) and below. Applications above 104°F(40°C) may require cables
larger than recommended, or cables rated higher than 167°F(75°C).
RECOMMENDED CABLE SIZES (RUBBER COVERED COPPER - RATED 167°F or 75°C)**
CABLE SIZES FOR COMBINED LENGTHS OF ELECTRODE AND WORK CABLES
AMPERES
200
200
225
225
250
250
250
250
300
325
350
400
400
500
PERCENT
DUTY
CYCLE
60
100
20
40 & 30
30
40
60
100
60
100
60
60
100
60
0 to 50Ft.
(0 to15m)
2
2
4 or 5
3
3
2
1
1
1
2/0
1/0
2/0
3/0
2/0
50 to 100Ft.
(15 to 30m)
2
2
3
3
3
2
1
1
1
2/0
1/0
2/0
3/0
2/0
100 to 150 Ft.
(30 to 46m)
2
2
2
2
2
1
1
1
1
2/0
2/0
2/0
3/0
3/0
150 to 200 Ft.
(46 to 61m)
1
1
1
1
1
1
1
1
1/0
2/0
2/0
3/0
3/0
3/0
200 to 250 Ft.
(61 to 76m)
1/0
1/0
1/0
1/0
1/0
1/0
1/0
1/0
2/0
3/0
3/0
4/0
4/0
4/0
TABLE A.1
A-2
INSTALLATION
A-2
SAFETY PRECAUTIONS
ELECTRIC SHOCK CAN KILL.
• Turn the input power OFF at the
disconnect switch or fuse box
before attempting to connect or
disconnect input power lines, out-
put cables or control cables.
• Only qualified personnel should
perform this installation.
• Do not touch metal portions of the LN25 PRO
EXTREME work clip when the welding power
source is on.
• Do not attach the work clip to the wire feeder.
• Connect the work clip directly to the work, as
close as possible to the welding arc.
• Turn power off at the welding power source
before disconnecting the work clip from the
work.
• Only use on power sources with open circuit
voltages less than 110 VDC.
------------------------------------------------------------------------
LOCATION
For best wire feeding performance, place the LN25
PRO EXTREME on a stable and dry surface. Keep
the wire feeder in a vertical position. Do not operate
the wire feeder on an angled surface of more than
15 degrees.
Do not submerge the LN25 PRO EXTREME.
The LN25 PRO EXTREME is rated IP23 and is
suitable for outdoor use.
The handle of the LN25 PRO EXTREME is intended
for moving the wire feeder about the work place
only.
When suspending a wire feeder, insulate the
hanging device from the wire feeder enclosure.
HIGH FREQUENCY PROTECTION
Locate the LN25 PRO EXTREME away from radio
controlled machinery. The normal operation of the
LN25 PRO EXTREME may adversely affect the oper-
ation of RF controlled equipment, which may result
in bodily injury or damage to the equipment.
--------------------------------------------------------------------------
LN-25 PRO EXTREME
WARNING
CAUTION