Miller Electric Belt/Hydraulic-Driven Generator Welding System User Manual


 
OM-4414 Page 9
4-3. Troubleshooting
Trouble Remedy
No generator output at platform
receptacles.
Be sure generator control switch is turned on at platform.
Check and secure electrical connections at platform, generator, and control box.
Be sure all equipment is turned off when starting unit.
Reset circuit breaker CB1 (see Section 4-2).
Check connections at receptacle RC3.
Be sure +12 volts dc input voltage is being supplied to control box.
Have Factory Authorized Service Agent check brushes, slip rings, and circuit boards PC1 and PC2.
Low generator output at platform
receptacles.
Verify generator is running at 3600 rpm.
Have Factory Authorized Service Agent check brushes, slip rings, and circuit boards PC1 and PC2.
High generator output at platform
receptacles.
Check control settings on welding equipment.
Verify generator is running at 3600 rpm.
Have Factory Authorized Service Agent check brushes, slip rings, and circuit boards PC1 and PC2.
Erratic generator output at platform
receptacles.
Check and secure electrical connections at platform, generator, and control box.
Verify generator is running at 3600 rpm.
Have Factory Authorized Service Agent check brushes, slip rings, and circuit boards PC1 and PC2.