Miller Electric DVI-2 R Welder User Manual


 
.A complete Parts List is available at www.MillerWelds.com
OM-232 386 Page 18
4-10. Electrical Service Guide For 230 VAC
Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.
60 Hz Single Phase
Input Voltage 230
Input Amperes At Rated Output 25
Max Recommended Standard Fuse Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
30
Normal Operating
3
35
Min Input Conductor Size In AWG
4
12
Max Recommended Input Conductor Length In Feet (Meters)
79
(24)
Min Grounding Conductor Size In AWG
4
12
Reference: 2005 National Electrical Code (NEC) (including article 630)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
4-11. Extension Cord Data
.When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
Input Voltage
Input Power
Phase
Hertz Conductor Size Max. Cord Length
115 V 1 60 10 AWG 34 ft (10 m)
230 V 1 60 12 AWG 79 ft (24 m)