3-11. Electrical Service Guide
Input Voltage 230 460 575
Input Amperes At Rated Output 69 34.5 27.5
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
80 40 30
Normal Operating 3 100 50 40
Min Input Conductor Size In AWG 4 4 8 10
Max Recommended Input Conductor Length In Feet (Meters)
237
(72)
422
(129)
444
(135)
Min Grounding Conductor Size In AWG 4 8 10 10
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.