SECTION 7 OPERATING AUXILIARY EQUIPMENT
7-1. 120 Volt And 240 Volt Duplex Receptacles
190 376
Y Be sure equipment connected to the
240 V receptacles is GFCI-pro-
tected.
. Generator power is not affected by
position of Welder Selector switch.
. 4 kVA/kW generator power output is
shared by all receptacles.
1 240 V 20 A AC Receptacle RC1
2 120 V 20 A AC GFCI Receptacle
GFCI 1
3 240 V 20 A AC Receptacle RC2
4 120 V 20 A AC GFCI Receptacle
GFCI 2
Receptacles supply 60 Hz single-phase
power at weld/power speed.
If a ground fault is detected, the GFCI re-
ceptacle(s) circuit opens to disconnect the
faulty equipment and the GFCI Reset but-
ton pops out. Check for damaged tools,
cords, plugs, etc. connected to the recep-
tacle. Press button to reset receptacle and
resume operation.
. At least once a month, run engine at
weld/power speed and press Test but-
ton to verify GFCI is working properly.
5 Circuit Breakers CB1 And CB2
6 Circuit Breakers CB3 And CB4
CB1 and CB2 protect RC1 and GFCI 1 from
overload. If CB1 or CB2 opens, RC1 does
not work. 120 volts may still be present at
RC1. If CB2 opens, GFCI 1 does not work.
Press button to reset breaker.
CB3 and CB4 protect RC2 and GFCI 2 from
overload. If CB3 or CB4 opens, RC2 does
not work. 120 volts may still be present at
RC2. If CB4 opens, GFCI 2 does not work.
Press button to reset breaker.
. If a circuit breaker continues to open,
contact Factory Authorized Service
Agent.
Maximum output from each 120 volt GFCI
receptacle is 2.4 kVA/kW. Maximum output
from each 240 volt duplex receptacle half is
4.0 kVA/kW.
Total combined output from all receptacles
is 4 kVA/kW.
EXAMPLE: If 12 A is drawn from RC1, only
9 A is available at GFCI 1:
(240 V x 12 A) + (120 V x 9 A) = 4.0 kVA/kW
. Generator power is not affected by
weld output.
152364
SECTION 8 MAINTENANCE & TROUBLESHOOTING
8-1. Routine Maintenance
Recycle
engine
fluids.
Y Stop engine before maintaining.
. See Engine Manual and Maintenance Label for im-
portant start-up, service, and storage information.
Service engine more often if used in severe condi-
tions.
* To be done by Factory Authorized Service Agent.
Every 8 h
Check Fluid
Levels. See
Section 5-5.
Wipe
Up
Spills.
Drain Water
From Fuel
System. See
Section 8-4.
OIL
Full
FUEL
WATER
Every 50 h
Clean Air Filter.
See Section 8-3.
Clean And
Tighten
Weld
Terminals.