2 INSTALLATION AND WIRING
NOTE
The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low as
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer
to page 8)
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit
to protect them from noise. (Refer to page 9)
Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are
connected, immediately remove them.
Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install options among the capacitor type
EMC filter FR-BIF (for use in the input side only), the ferrite core type EMC filter FR-BSF01/FR-BLF, filterpack, and EMC
filter to minimize the interference. ( Refer to Chapter 3 of the Instruction Manual (Applied)).
Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
EMC filter (ferrite core)
(FR-BSF01, FR-BLF)
Install
an EMC filter (ferrite core)
to reduce the electromagnetic
noise generated from the inverter.
Effective in the range from about
1MHz to 10MHz. A wire should be
wound four turns at a maximum.
Motor
Earth (Ground)
Earth (Ground)
Devices connected to the output
Do not install a power factor correction capacitor,
surge suppressor or capacitor type filter on the output
side of the inverter. When installing a moulded case
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
moulded case circuit breaker.
The regenerative braking capability
of the inverter can be exhibited fully.
Install this as required.
Power supply harmonics
can be greatly suppressed.
Install this as required.
High power factor
converter (FR-HC)
Power regeneration
common converter
(FR-CV)
Earth (Ground)
R/L1S/L2T/L3
P1
UW
PR
V
Great braking capability
is obtained.
Install this as required.
EMC filter (ferrite core) *
(FR-BSF01, FR-BLF)
AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a moulded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
Moulded case circuit breaker
(MCCB) or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
inverter at power ON.
Install
an EMC filter (ferrite core)
to reduce the electromagnetic
noise generated from the
inverter. Effective in the range
from about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained. A wire should
be wound four turns or more.
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earthing cable by returning it to the earth
(ground) terminal of the inverter.
AC reactor (FR-HAL)
DC reactor (FR-HEL) *
EMC filter
(capacitor) *
(FR-BIF)
P/+
P/+
PR
PR
Brake unit
(FR-BU2)
Reduces the
radio noise.
Resistor unit (FR-BR)
Discharging resistor (GZG, GRZG)
Inverter (FR-E700)
* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.
Approved safety
relay module
Required for
compliance with
safety standard.
S1
S2
SC
Parameter unit
(FR-PU07)
USB connector
A personal computer and an inverter
can be connected with a
USB (Ver1. 1) cable.
Enclosure surface operation panel
(FR-PA07)
By connecting the connection cable (FR-
CB2) to the PU connector, operation can
be performed from FR-PU07, FR-PA07.
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when
power harmonics measures are taken,
the power factor is to be improved or the
inverter is installed near a large power
supply system (500kVA or more). The
inverter may be damaged if you do not
use reactors. Select the reactor according
to the model. Remove the jumpers across
terminals P/+ and P1 to connect the DC reactor.
P/+
P/+
P/+
N/-
(Refer to page 46)
(Refer to page 7)
(Refer to page 7)
( Refer to Chapter 4 of the
Instruction Manual (Applied))
Brake resistor
(FR-ABR, MRS type, MYS type)
Braking capability can be improved. (0.4K
or higher)
Always install a thermal relay when using
a brake resistor whose capacity is 11K or
higher.
(Refer to page 19)