FP-AI-112 and cFP-AI-112 12 ni.com
Physical Characteristics
Indicators ..........................................Green POWER and
READY indicators
Weight
FP-AI-112...................................142 g (5.0 oz)
cFP-AI-112.................................113 g (4.0 oz)
Power Requirements
Power from network module ............350 mW
Isolation Voltage
Channel-to-ground isolation
Continuous .................................250 V
rms
,
Installation Category II
Dielectric withstand....................2,300 V
rms
, 1 minute
Channel-to-channel isolation............None
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature ......................–40 to 70 °C
Storage temperature..........................–50 to 85 °C
Humidity...........................................10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered.
Pollution Degree...............................2