Outback Power Systems FX2024ET Battery Charger User Manual


 
6
Use the search sensitivity screen to determine the
size of an AC load needed for the FX to turn ON
and leave SEARCH mode.
• Pressing decreases sensitivity (a bigger
load is needed to turn the FX on)
• Pressing increases the sensitivity which
means a smaller load (less wattage) will turn
the FX on
• Decreasing to zero disables SEARCH mode
Press to view the next SEARCH screen.
The FX produces pulses to detect AC loads. The
search pulse length screen allows adjusting the
number of pulses (from 2 to 20) or cycles to
more reliably detect AC loads. A setting of 8 or
higher, adjusted using and ,
is recommended. Press to open the
search pulse spacing screen.
The search pulse spacing screen adjusts the
amount of time the FX waits before producing
additional AC pulses to sense a load. The higher
the number of cycles, the lower the FX power
consumption, but the longer it takes before the
AC load is powered. The cycles range from 4 to
120 cycles (two seconds). Press the to
complete the SEARCH menu.
SETUP/FX/SEARCH--------P00
search 6
sensitivity
DOWN INC DEC PORT
SETUP/FX/SEARCH--------P00
search 8 cycles
pulse length
DOWN INC DEC PORT
SEARCH MODE
An FX consumes a small amount of power when it is not providing AC to loads or recharging
batteries. In SEARCH MODE, the FX is inactive and conserves power until it senses a user-determined
size load. The FX then turns on to provide AC to that load. The SEARCH features are mainly used in o -
grid systems to conserve power.
NOTE: Some loads will require experimenting with the SEARCH settings and other loads, such as
uorescent lights with magnetic ballasts, might not work well at all.
SETUP/FX/SEARCH--------P00
search 60 cycles
pulse spacing
DOWN INC DEC PORT
INC
DEC
DOWN
DECINC
DOWN
DOWN