Outback Power Systems GFX1448E Battery Charger User Manual


 
Specifications
900-0112-01-00 Rev A 45
Table 18 24-Volt Inverter Settings
24 Vdc Inverter Default Minimum Maximum
Grid
AC1/Grid Lower Limit
208 Vac 140 Vac 220 Vac
AC1/Grid Upper Limit
252 Vac 250 Vac 280 Vac
AC1/Grid Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
Generator (Gen)
Gen Input Connect Delay
0.5 min 0.2 min 15 min
AC2/Gen Lower Limit
208 Vac 140 Vac 220 Vac
AC2/GenUpper Limit
252 Vac 250 Vac 280 Vac
AC2/Gen Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
AC2/Gen Support ON ON or OFF
Auxiliary (AUX)
AUX Output Control AUTO ON, OFF, or AUTO
AUX Output Function Cool Fan Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
GenAlert On Voltage
22 Vdc 20 Vdc 28 Vdc
GenAlert On Delay
4 min 0 min 240 min
GenAlert Off Voltage
28 Vdc 24 Vdc 36 Vdc
GenAlert Off Delay
9 min 0 min 240 min
Load Shed Off Voltage
22 Vdc 20 Vdc 28 Vdc
Vent Fan On Set Point
26 Vdc 20 Vdc 32 Vdc
Vent Fan Off Period
5 min 0 min 30 min
Diversion On Voltage
29.2 Vdc 24 Vdc 32 Vdc
Diversion Off Delay
30 sec 0 sec 240 sec
Stacking
Stack Phase Master Master, OB Slave L1, 3p Classic B, or 3p Classic C
Power Save Level
Master Adjust Only
0 0 7
Slave Adjust Only
1 1 15
Sell
Sell RE Volts
26 Vdc 20 30
Grid Tie Window IEEE IEEE or User
Grid Tie Authority GridTie GridTie or No Sell
Calibration (Cal)
Vac Input Adjustment
236 220 254
Vac Output Adjustment
236 220 254
Battery Vdc Adjustment
2 0 4
These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower
voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal, and 17 Vac below
nominal.
These values are in digital counts, not volts. One count equals 0.2Vdc. The range of adjustment is 0.4 Vdc above or below
nominal.