Outback Power Systems GFX1448E Battery Charger User Manual


 
Specifications
46 900-0112-01-00 Rev A
Table 19 48-Volt Inverter Settings
48 Vdc Inverter Default Minimum Maximum
Search
Search Sensitivity
(see page 14 for increments)
6 0 50
Search Pulse Length
8 4 20
Search Pulse Spacing
60 AC cycles 4 AC cycles 120 AC cycles
Input
AC Transfer Control Grid Grid or Generator
AC1/Grid Limit
25 Aac 2.5 Aac 30 Aac
AC2/Gen Limit
25 Aac 2.5 Aac 30 Aac
Inverter
Low Battery Cut-Out (LBCO)
42 Vdc 36 Vdc 48 Vdc
Low Battery Cut-In (LBCI)
50 Vdc 40 Vdc 56 Vdc
Adjust Output Voltage
230 Vac 210 vac 250 Vac
Charger
Charger Limit
5.5 Aac 0 Aac 6Aac
Absorb Voltage
57.6 Vdc 52 Vdc 64 Vdc
Absorb Time Limit
1.0 hours 0.0 hours 24.0 hours
Float Voltage
54.4 Vdc 48 Vdc 60 Vdc
Float Time Period
1.0 hours 0.0 hours 24.0 hours
ReFloat Voltage
50 Vdc 48 Vdc 52 Vdc
Equalization Voltage
58.4 Vdc 56 Vdc 68 Vdc
Equalization Time Period
1.0 hours 0.0 hours 24.0 hours
Grid
AC1/Grid Lower Limit
208 Vac 140 Vac 220 Vac
AC1/Grid Upper Limit
252 Vac 250 Vac 280 Vac
AC1/Grid Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
Generator (Gen)
Gen Input Connect Delay
0.5 min 0.2 min 15 min
AC2/Gen Lower Limit
208 Vac 140 Vac 220 Vac
AC2/GenUpper Limit
252 Vac 250 Vac 280 Vac
AC2/Gen Transfer Delay
6 AC cycles 0 AC cycles 240 AC cycles
AC2/Gen Support ON ON or OFF
Auxiliary (AUX)
AUX Output Control AUTO ON, OFF, or AUTO
AUX Output Function Cool Fan Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
GenAlert On Voltage
44 Vdc 40 Vdc 56 Vdc
GenAlert On Delay
4 min 0 min 240 min
GenAlert Off Voltage
56 Vdc 48 Vdc 72 Vdc
GenAlert Off Delay
9 min 0 min 240 min
Load Shed Off Voltage
44 Vdc 40 Vdc 56 Vdc
Vent Fan On Set Point
52 Vdc 40 Vdc 64 Vdc
Vent Fan Off Period
5 min 0 min 30 min
Diversion On Voltage
58.4 Vdc 48 Vdc 64 Vdc
Diversion Off Delay
30 sec 0 sec 240 sec