Outback Power Systems GTFX Battery Charger User Manual


 
ADV/FX/AUX---------------P00
genalert 11.5vdc
on setpoint
DOWN INC DEC PORT
• From the Remote aux output function screen, press
the <DOWN> soft key. This will bring up the rst of
several screen used to adjust which ever mode you
have chosen for the AUX function.
ADV/FX/AUX-------------P00
aux output Remote
function
DOWN INC DEC PORT
• The genalert on setpoint functions are not available
for grid-interactive FXs. Press the <DOWN> soft key
three times to view the loadshed o setpoint screen.
• The loadshed o setpoint is the battery voltage
which triggers the AUX to reduce the inverter and
battery loads. When the battery voltage drops below
this value for three seconds, the AUX powers a DC
coil relay to disconnect an AC load. Once triggered,
loadshed remains on for at least three minutes. The
loadshed o setpoint is adjustable from10 VDC-14
VDC in 0.1 VDC increments using the <INC> and
<DEC> soft keys. Press the <DOWN> soft key to
bring up the ventfan on setpoint.
• When the AUX is set to ventfan, a fan ventilates
a battery enclosure. The ventfan on setpoint
establishes the battery voltage which energizes the
AUX and thus the fan for a one minute period. The
voltage setting has a range of 10.0 VDC-16.0 VDC in
0.1 VDC increments using the <INC> and <DEC>
soft keys. Recharging causes batteries to emit mostly
hydrogen gas; higher recharging voltages emit more
gas. Press the <DOWN> soft key to view the ventfan
o period screen.
ADV/FX/AUX---------------P00
loadshed 11.0 vdc
o setpoint
DOWN INC DEC PORT
ADV/FX/AUX---------------P00
ventfan 13.0 vdc
on setpoint
DOWN INC DEC PORT
21