• If a ventilation fan is only needed intermittently,
the ventfan o period shuts the fan o for a user-
determined time before starting up again for a one-
minute period when the battery voltage exceeds
the ventfan on setpoint. This o period can be set
from 0-30 minutes in one-minute increments using
the <INC> and <DEC> soft keys. Setting this period
to zero will keep the fan running the entire time
the battery voltage is high enough to activate the
ventfan function. Setting it to ve minutes means the
fan will run for one minute and then shut o for ve
minutes until the battery voltage drops and the fan
is no longer needed. Press the <DOWN> soft key to
view the diversion on setpoint screen.
ADV/FX/AUX---------------P00
ventfan o 5 min
period
DOWN INC DEC PORT
• After deciding on Divert DC or Divert AC, use the
diversion on setpoint screen to choose the voltage
which will activate this AUX OUTPUT FUNCTION.
This value can range from 12.0 VDC-16.0 VDC and
can be adjusted in 0.1 VDC increments using the
<INC> and <DEC> soft keys. Press the <DOWN>
soft key to view the diversion o delay screen.
ADV/FX/AUX---------------P00
diversion 14.6 vdc
on setpoint
DOWN INC DEC PORT
• The diversion o relay determines how long the AUX
will be energized after the battery voltage which
caused the diversion falls below the diversion on
setpoint. This delay can range from 0-240 seconds in
one-second increments as adjusted with the <INC>
and <DEC> soft keys.
ADV/FX/AUX--------------P00
diversion 30 sec
o delay
DOWN INC DEC PORT