Outback Power Systems VFX2612E Battery Charger User Manual


 
45
ADV/FX/AUX--------------P00
genalert 9 min
o delay
DOWN INC DEC PORT
After a battery has recharged or returned to
the genalert o set point, genalert o delay
determines the amount of time the generator
remains on to assure the battery has been more
fully recharged. The user can adjust this time
from 0-240 minutes in using the <INC> and <DEC>
soft keys. Press the <DOWN> soft key to view the
loadshed o set point screen.
ADV/FX/AUX---------------P00
loadshed 11.0 vdc
o set point
DOWN INC DEC PORT
The loadshed o set point is the battery voltage
which triggers the AUX to reduce the inverter
and battery loads. When the battery voltage
drops below this value for three seconds, the
AUX powers a DC coil relay to disconnect an AC
load. Once triggered, loadshed remains on for at
least three minutes. The loadshed o set point
is adjustable from10 VDC-14VDC using the <INC> and
<DEC> soft keys. Press the <DOWN> soft key to bring
up the ventfan on set point.
ADV/FX/AUX--------------P00
ventfan 13.0 vdc
on set point
DOWN INC DEC PORT
Recharging causes batteries to emit mostly hydrogen
gas. When the AUX is set to ventfan, a fan ventilates
a battery enclosure. The ventfan on set point establishes
the battery voltage which energizes the AUX and thus
the fan for a one minute period. The voltage setting has
a range of 10.0VDC-16.0VDC in 0.1 VDC increments
using the <INC> and <DEC> soft keys. Press the
<DOWN> soft key to view the ventfan o period screen.
ADV/FX/AUX--------------P00
ventfan o 5 min
period
DOWN INC DEC PORT
If a ventilation fan is only needed intermittently,
the ventfan o period shuts the fan o for a user-
determined time before starting up again for a one-
minute period when the battery voltage exceeds the
ventfan on set point. This o period can be set from
0-30 minutes using the <INC> and <DEC> soft keys.
Setting this period to zero will keep the fan running
the entire time the battery voltage is high enough to
activate the ventfan function. Setting it to  ve minutes
means the fan will run for one minute and then shut
o for  ve minutes until the battery voltage drops and
the fan is no longer needed. Press the <DOWN> soft
key to view the diversion on set point screen.