STUDER INNOTEC HP-COMPACT
User manual HP-COMPACT V3.0 E 20
4.11 Remote control for „Power Sharing“
If the Remote control RPS-01 is installed, the Trimmer (26) “INPUT LIMIT“ has to be set
on the value max.. The HP-COMPACT takes into account the lowest values set on the
inverter and on the Remote control.
The current available at the HP-COMPACT input will be de-
termined by the power of the connected source (generator,
grid etc...). The potentiometer on the RPS-01 must be ad-
justed lower or equal to max. value of the power source.
For instance if the source is a generator of 2000 Watt, the
potentiometer has to be set at max. 8A. This value is ob-
tained in dividing 2000 Watt by 230V. If the HP-COMPACT
is connected to a power source which is protected by a 6A
circuit breaker, the potentiometer must be set at a max.
value of 6A.
Caution: the HP-COMPACT will not limit if an appliance draws more current than
available from the source ! This means that the connected generator will be over-
loaded or that the circuit-breaker before the HP-COMPACT will break.
5 Programming
5.1 Standard setting
The HP-COMPACT is delivered with the following default setting:
5.1.1 Battery voltage
Low voltage 11.6V / 23.2V / 46.4V
Float Charge 13.5V / 27.0V / 54.0V
End of Charge Voltage 14.4V / 28.8V / 57.6V
Equalization 15.3V / 30.6V / 61.2V
Absorption Time: 2 Hours
5.1.2 Auxiliary contact
Active in case of defect or manual turn off with the LED 10/11/12/13.
5.2 Reset value
When the HP-COMPACT is to be connected to a battery or after an interruption (RESET),
it is always programmed with these standard settings (see above).
In order to get to these settings during operation you must press the three Push Buttons
19/20/21 simultaneously for a minimum of 2 seconds.
5.3 Battery voltages and absorption time
The voltage levels (low voltage, float charge, end of charge and equalization) and the du-
ration of the absorption charge can be changed.
The display of these voltages and the times in the program mode are in accordance with
the diagram shown below:
5.3.1 Table of voltage and timing threshold